SI0034 (203) - SOFTWARE ENHANCEMENTS EFFECTIVE AUGUST 2002 (CONT'D)
Chiller Mod –
Compressor
"Mod C, D, E –
G, H, J Compr"
"Mod E – P Compr"
Limit Switch
"Mod F –
Limit Switch
G, H Compr"
"Mod F – J Compr"
"Mod F – P Compr"
Limit Switch
* Not applicable to Mod C and earlier chillers.
Factory Mounted Flow Sensors
Style "F" (and later) chillers are supplied with factory-mounted Flow Sensors on the evaporator and condenser.
These are electronic thermal-type sensors. The operating principle of the sensor is thermal conductivity. It uses the
cooling effect of a fl owing liquid to sense fl ow. The temperature of the heated sensor tip is sensed by a thermistor
located in the tip.
A second thermistor, located higher in the tip in a non-heated area, is only affected by changes in liquid temperature.
The temperatures sensed by the thermistors are compared. Flowing liquid carries heat away from the heated sensor
tip, lowering its temperature. The lower temperature differential between the two thermistors indicates the liquid is
fl owing. A higher differential indicates no fl ow. Each device operates from a 24Vac power source and has a solid
state relay output. On each sensor, one side of the solid state relay output (pin 2) is connected to the microboard
+5Vdc and the other side (pin 4) is connected to a microboard analog input.
When fl ow is sensed, the solid state relay output is turned on causing it to conduct current through the 7.5K ohm
microboard load resistor to the +5vdc. This applies >+4Vdc to the microboard input (evaporator J7-14; condenser
J7-16). When no fl ow is sensed, the solid state relay output is turned off, resulting in no conduction through the load
resistor. This applies <1Vdc to the microboard input. To determine the state of the solid state relay, fi rst confi rm that
+5vdc is present at pin 2 of the fl ow sensor. Then connect a voltmeter from Microboard J7-14 (evaporator) or J7-16
(condenser) to microboard TP1 (ground).
The power source is connected to the sensor as follows:
From
To
Sensor pin 1
TB1-162 (24Vac)
pin 3
TB6-5 (Gnd)
The sensor outputs are connected to the Microboard as follows:
Evaporator:
From
Sensor pin 2
pin 4
Condenser:
Sensor pin 2
pin 4
Microboard Program Jumpers JP21 and JP22 must be placed in the positions 2 & 3.
YORK INTERNATIONAL
Oil
Proxmity
Control
Heater
Sense
Output*
Probe
TB1-34
TB1-64
10.0 sec
TB1-64
Probe
TB1-64
TB1-64
10.0 sec
To
Microboard J7-1 (+5Vdc)
J7-14 (input to Microboard )
Microboard J7-15 (+5Vdc)
J7-16 (input to Microboard)
Level
Flow
Period
Switch
Default
3.5 sec
Paddle Type
Paddle Type
Factory Mounted
3.5 sec
Thermal Type
Factory Mounted
3.5 sec
Thermal Type
Factory mounted
Thermal Type
FORM 160.54-M1(503)
"Oil-Variable Speed
Pump Pressure Setpoint
Not Achieved" Threshold*
35 PSID
25 PSID
35 PSID
35 PSID
25 PSID
175
26