Power and Control Panel Layouts ....................... 35 SECTION COMMISSIONING Preparation ............................37 Preparation - Power Off ......................... 37 First Time Start-up ..........................39 SECTION OPERATION General Description ..........................40 Start-up ............................40 Normal Running and Cycling ....................... 40 Shutdown ............................40 YORK INTERNATIONAL...
Page 4
Program Key - User Programmable Values ............... 136 Programming "Default" Values .................... 139 Condenser Fan Control ......................141 SECTION MAINTENANCE General Requirements ........................142 Daily Maintenance .......................... 142 Scheduled Maintenance ........................ 142 Chiller/Compressor Operating Log ....................143 Maintenance Requirements ......................144 YORK INTERNATIONAL...
Page 5
TABLE 2 - Condenser Fan Control and Fan Contactor Data for DXST Units with 4 Fans System ..141 TABLE 3 - Condenser Fan Control and Fan Contactor Data for DXST Units with 5 Fans System ..141 YORK INTERNATIONAL...
NOT be installed inside the micro panel. NO external wiring is allowed to be run through the micro panel. All wiring must be in accordance with YORK’s published specifications and must be performed ONLY by qualified YORK personnel. YORK will not be responsible for damages/problems resulting from improper connections to the controls or application of improper control signals.
FORM 201.18-NM2 CHANGEABILITY OF THIS DOCUMENT In complying with YORK’s policy for continuous prod- It is the responsibility of operating/service personnel uct improvement, the information contained in this as to the applicability of these documents to the equip- document is subject to change without notice. While ment in question.
Standards for Safety only be performed by suitably trained and qualified personnel. Millennium YCAS chillers are designed and built within an ISO 9002 accredited design and manufacturing or- The manufacturer will not be liable for any injury or ganization. The chillers comply with the applicable sec-...
This manual, and any other document supplied with the age to the pressure system. No attempt should be made unit, are the property of YORK which reserves all rights. to gain access to the component parts of the pressure They may not be reproduced, in whole or in part, with-...
When operated, each removes The build-up of refrigerant vapor, from a leak for ex- the electrical supply from the control system, thus shut- ample, does pose a risk of asphyxiation in confined or ting down the unit. YORK INTERNATIONAL...
Fire Extinguishing Data Non-flammable. Containers Fire exposed containers should be kept cool with water sprays. Containers may burst if overheated. Fire Fighting Self-contained breathing apparatus and protective clothing must be worn in fire conditions. Protective Equip. YORK INTERNATIONAL...
Page 12
General Chiller Information & Safety MATERIAL SAFETY DATA Section 1 – PRODUCT NAME AND INFORMATION Product (Trade Name and Synonyms): YORK “L” Oil Chemical Name: Ester Chemical Family: Polyol Ester Formula: Proprietary CAS#: Proprietary Section 2 – COMPONENTS AND HAZARD STATEMENT This product is non-hazardous.
Page 13
The information in this material safety data sheet should be provided to all who use, handle, store, transport, or are otherwise exposed to this product. CPI believes the information in this document to be reliable and up to date as of the date of publication, but makes no guarantee that it is. YORK INTERNATIONAL...
3 mm (1/8") either side of a scribed line (equivalent to ASTM D1654 rating of “6”). YORK Millennium YCAS chillers are designed for All exposed power wiring is be routed through liquid- water or water-glycol cooling. All units are designed to tight, non-metallic conduit.
–29ºC (–20ºF) ambient and in- sulated with flexible closed-cell foam. The water nozzles are provided with grooves for me- chanical couplings and should be insulated by the con- tractor after pipe installation. LD03674 FIG. 2 – SCREW COMPRESSOR YORK INTERNATIONAL...
Page 16
The wet vapor to the economizer is supplied by a small The oil (YORK “L” oil - a POE oil used for all refriger- 15 ton TXV set for 5.5ºC (10ºF) superheat that flashes ant applications), which drains back into the compres- off 10- 20% of the liquid from the condenser.
Page 17
The panel enclosures are de- mal storage, automatic pump down, run signal contacts, demand load limit from external building automation sys- signed to IP55 and are manufactured from powder painted galvanized steel. tem input, remote reset liquid temperature reset input, YORK INTERNATIONAL...
Page 18
Since the micro is sending a run signal to the contactor, The 2ACE module design uses one integral current trans- it senses the low motor current below 10% FLA and former per phase to provide protection against rapid shuts the system down. YORK INTERNATIONAL...
Page 19
(High Phase - Low Phase) / High Phase position requires pushing the switch to the left. Improper Phase Sequence It is recommended that a YORK Ser- vice Technician or the YORK factory The 2ACE module calculates the phase sequence at...
1S (SYS 1) or 2S (SYS 2) contacts, energiz- Entry – Used to confirm Set Point changes, cancel in- ing motor contactor 2M (SYS 1) or 4M (SYS 2), com- puts, advance day, and change AM/PM. pleting the “DELTA” connection of the motor. YORK INTERNATIONAL...
Printed circuit board to accept 4 to 20 mA, 0 to 10 VDC, ACCESSORIES AND OPTIONS or dry contact closure input from the BAS. A YORK ISN Building Automation System can pro- Multiple Point Power Connection (Standard) vide a Pulse Width Modulated (PWM) signal direct to...
51 mm (2"). Level adjustable, deflec- heavy gauge welded wire mesh guards mounted around tion may vary slightly by application. (Field mounted). the bottom of the unit (Factory or field mounted). YORK INTERNATIONAL...
FIG. 4 – LIFTING LUGS Major damage must be reported immediately to your local YORK representative. The unit must only be lifted by the base frame at the points provided. Never move the unit on roll- ers, or lift the unit using a fork-lift truck.
120 mm tion the same requirement of static pressure loss ap- (4-3/4") wide at the contact points. This will allow vibra- plies as for ducts and attenuators stated above. tion isolators to be fitted if required. YORK INTERNATIONAL...
1" N.P.T. connection can be obtained with each unit. from YORK as an accessory for the unit. Alternatively, a differential pressure switch sited across an orifice plate Using the Isolator tables (pages 76 - 82), refer to the may be used, preferably of the high/low limit type.
Aerated, brackish or salt water is not recommended for low and high points in the pipework to permit drainage use in the water system(s). YORK recommends that a of the system and to vent any air in the pipes. water treatment specialist is consulted to determine that...
It is recommended that a piece of pipe is fitted to each Where cross winds may occur, any ductwork must be valve and directed so that when the valve is activated the supported to prevent side loading on the unit. YORK INTERNATIONAL...
This will prevent recircu- tion (not supplied by YORK). lation of air when only one of the fans is running. Units are supplied with outlet guards for safety and to prevent damage to the fan blades.
Page 34
RS 232 port. the customer master start/stop so that the YORK con- tact can start the pump in the event of a low tempera- Remote Set Point Offset - Temperature ture liquid condition.
Flow Switch System No. 1 Run System No. 1 Alarm Contacts System No. 2 Run Current Chilled Liquid Circulating Pump Start Temperature System No. 2 Print Alarm Contacts Chiller Run Isolator Auxiliary Interlock LD03502 FIG. 9 – CUSTOMER CONNECTIONS YORK INTERNATIONAL...
Verify that the site voltage supply corresponds to the Compressor Oil unit requirement and is within the limits given in the Tech- To add oil to a circuit - connect a YORK hand oil pump nical Data Section. (Part No. 470-10654-000) to the 6 mm (1/4”) oil charg-...
Page 38
(offset) is to be used, the maximum reset must be pro- limits given in the Technical Data Section. Operation grammed by pressing the ‘Remote Reset Temp’ key. outside of these limits is undesirable and could cause (See Section 6.) damage. YORK INTERNATIONAL...
When all run cor- erant is in the system, the bubbles will disappear and be rectly, stop the unit, switch all applicable switches to the replaced by a solid column of liquid. ‘ON’ position and restart the unit. YORK INTERNATIONAL...
The units are designed to work independently, or in con- automatic. After an initial period at minimum capacity junction with other equipment via a YORK ISN build- on the lead compressor, the control system will adjust ing management system or other automated control sys- the unit load depending on the chilled liquid temperature tem.
1. For leaving brine temperature below 4.4°C, contact your nearest YORK office for application requirements. 2. For leaving water temperature higher than 13°C, contact the nearest YORK office for application guidelines. 3. The evaporator is protected against freeze-up to -28.8°C with an electrical heater as standard.
(see correction factors to be applied 1.25 when using glycol solutions). Special care must be taken 1.20 not to exceed the maximum allowed. 1.15 1.10 1.05 Correction Factor Mean Temperature through Cooler PROPYLENE GLYCOL Concentration W/W LD03504 FIG. 11 – GLYCOL CORRECTION FACTORS YORK INTERNATIONAL...
PRESSURE (Pa) HIGH PRESS. FANS OPTION 2 SLOW SPEED FANS ELECTRICAL THREE PHASE 50 Hz (V) * Maximum Ambient w/ High Ambient Kit is 52ºC. SOUND POWER DATA (PRELIMINARY) MODEL YCAS 0373EC 0403EC 0453EC 0503EC 0543EC 0573EC 0623EC 0653EC YORK INTERNATIONAL...
Maximum Refrigerant Side Pressure, Bar Minimum Chilled Water Flow Rate, l/sec. 10.9 11.4 11.4 12.1 13.4 Maximum Chilled Water Flow Rate, l/sec. 37.9 37.9 37.9 37.9 47.1 47.1 47.1 47.1 Water Connections, inches Optional 21 Bar Waterside available YORK INTERNATIONAL...
Maximum Refrigerant Side Pressure, Bar Minimum Chilled Water Flow Rate, l/sec. 10.9 11.4 11.4 12.1 13.4 Maximum Chilled Water Flow Rate, l/sec. 37.9 37.9 37.9 37.9 47.1 47.1 47.1 47.1 Water Connections, inches Optional 21 Bar Waterside available YORK INTERNATIONAL...
Y-D D D D D Start and Across-The-Line Start SEE NOTE 2 LD04106 OPTIONAL SINGLE-POINT POWER SUPPLY WITH INTERNAL UNIT CIRCUIT BREAKERS Optional Field Provided 115-1Ø MicroPanel Supply Suitable for: Y-D D D D D Start and Across-The-Line Start SEE NOTE 2 LD04107(50) YORK INTERNATIONAL...
1. – – – – – – – Dashed Line indicates Field Provided Wiring. 2. The above recommendations are based on the National Electrical Code and using copper conductors only. Field wiring must also comply with local codes. YORK INTERNATIONAL...
Transient Voltage Suppression Terminal Block for Customer Connections Terminal Block for Customer Low Voltage (Class 2) Connections. See Note 2 Terminal Block for YORK Connections Only Wiring and Components by YORK Optional Equipment Wiring and/or Components by Others FIG. 12 – ELEMENTARY DIAGRAM – ACROSS-THE-LINE START...
Page 53
FORM 201.18-NM2 WIRING DIAGRAM ACROSS-THE-LINE START YORK INTERNATIONAL...
Page 54
Technical Data ELEMENTARY DIAGRAM FIG. 12 – CONTINUED YORK INTERNATIONAL...
Page 55
Any contacts connected to flow switch inputs or BAS inputs on terminals 13 - 19 or TB3, or any other terminals, must be sup- pressed with a YORK P/N 031- 00808-000 suppressor across the relay/contactor coil. CAUTION: Control wiring connected to...
Transient Voltage Suppression Terminal Block for Customer Connections Terminal Block for Customer Low Voltage (Class 2) Connections. See Note 2 Terminal Block for YORK Connections Only Wiring and Components by YORK Optional Equipment Wiring and/or Components by Others FIG. 15 – ELEMENTARY DIAGRAM – WYE-DELTA START...
Page 59
FORM 201.18-NM2 WIRING DIAGRAM WYE-DELTA START FIG. 15 – CONT’D LD03229 YORK INTERNATIONAL...
Page 60
Technical Data ELEMENTARY DIAGRAM FIG. 15 – CONTINUED YORK INTERNATIONAL...
Page 61
Any contacts connected to flow switch inputs or BAS inputs on terminals 13 - 19 or TB3, or any other terminals, must be sup- pressed with a YORK P/N 031- 00808-000 suppressor across the relay/contactor coil. CAUTION: Control wiring connected to the...
Technical Data LEGEND – FIGS. 12 THROUGH 16 CONNECTION DIAGRAM ELECTRIC BOX DXST DIRECT DRIVE FIG. 18 – CONNECTION DIAGRAM LD03281 YORK INTERNATIONAL...
Site restrictions may compromise minimum clearances indicated below, resulting in unpre- dictable air flow patterns and possible diminished performance. YORK's unit controls will optimize operation without nuisance high pressure safety cutout; however, the system designer must consider potential performance degradation. Access to the unit control center assumes the unit is no higher than on spring isolators.
Site restrictions may compromise minimum clearances indicated below, resulting in unpre- dictable air flow patterns and possible diminished performance. YORK's unit controls will optimize operation without nuisance high pressure safety cutout; however, the system designer must consider potential performance degradation. Access to the unit control center assumes the unit is no higher than on spring isolators.
Page 73
FORM 201.18-NM2 LD02994 CENTER OF GRAVITY (Alum.) CENTER OF GRAVITY (Copper) YCAS YCAS 0543 2717.8 1087.1 914.4 0543 2755.9 1092.2 988.1 0573 2717.8 1097.3 914.4 0573 2753.4 1097.3 988.1 0623 2717.8 1097.3 914.4 0623 2753.4 1097.3 988.1 2718 LD02995 YORK INTERNATIONAL...
Page 74
Site restrictions may compromise minimum clearances indicated below, resulting in unpre- dictable air flow patterns and possible diminished performance. YORK's unit controls will optimize operation without nuisance high pressure safety cutout; however, the system designer must consider potential performance degradation. Access to the unit control center assumes the unit is no higher than on spring isolators.
Page 75
FORM 201.18-NM2 LD03004 CENTER OF GRAVITY (Alum.) CENTER OF GRAVITY (Copper) YCAS YCAS 0653 3032.8 1097.3 965.2 0653 3106.4 1099.8 1041.4 LD03005 YORK INTERNATIONAL...
1/4" shim be- ance of 1/8" between resilient washer and under- tween the upper load plate and vertical uprights. side of channel cap plate. Lower the equipment on the blocking or shimmed 10. Installation is now complete. isolators. YORK INTERNATIONAL...
FORM 201.18-NM2 CLEARANCES 1.3 m (48") (72") LD03484 Notes: No obstructions allowed above the unit. Only one adjacent wall may be higher than the unit. Adjacent units should be 3 meters (10 feet) apart. FIG. 29 – CLEARANCES YORK INTERNATIONAL...
The high pressure oil-free vapor is fed to the Air- place before returning to the cooler. cooled condenser coil and fans where the heat is removed. The fully condensed liquid enters the economizer. FIG. 30 – REFRIGERANT FLOW DIAGRAM YORK INTERNATIONAL...
STATOR LOCKING BOLT OIL FILTER COVER PLATE OIL FILTER BLEED & EVACUATION POINT LIFTING LUG THREADED HOLE HEATER ECONOMIZER GAS IN DISCHARGE CASE DISCHARGE GAS OUT OIL INLET FROM CONDENSER CODING COIL LD03668 FIG. 33 – COMPRESSOR COMPONENTS YORK INTERNATIONAL...
START-UP If it is necessary to add oil, connect a YORK oil TECHNICIAN/ pump to the charging valve on the oil separator, COMPANY: _______________________________...
Page 94
4. Check the system operating parameters. Do this Dischg Press Cut-out = ____________ kPa (PSIG) by selecting various displays such as pressures Disch Press Unld = _______________ kPa (PSIG) and temperatures. Compare these to test gauge readings. Suction Press Cut-out = ____________ kPa (PSIG) YORK INTERNATIONAL...
Page 95
____ ____ ____ (KPA)(PSIG) Superheat = ____ ____ ____ ____ °C (0°F) Temp = ____ ____ ____ ____ °C (°F) Liq Line Temp = ____ ____ ____ ____ °C (°F) Subcooling = ____ ____ ____ ____ °C (°F) YORK INTERNATIONAL...
Page 96
(approximately 15 minutes) between adjust- ments for the system and the thermal expansion valve to respond and settle out. Assure that superheat is set between 6-7°C (10 -12°F). YORK INTERNATIONAL...
This switch shuts down the entire chiller when placed in This key is used for display and programming of the the OFF position. The switch must be ON for the chiller chiller operational settings and limits. to operate. YORK INTERNATIONAL...
External interface is available for control of the chiller to turn the entire chiller OFF, if desired. The switch via a YORK ISN System or YORK Remote Control must be placed in the ON position for the chiller to op- Center.
One Relay Output Board per system operates the mo- While a chiller is operating, the clock must be ON (Sec- tor contactors / starters, solenoid valves, and heaters tion 1.11, Item 1) or the internal clock on the micropro- which control system operation. YORK INTERNATIONAL...
Power Supply Board which rectifies and filters the signals to variable DC Voltage (analog). These The module also provides phase rotation protection to analog levels are then fed to the Microprocessor Board assure the screw compressor does not rotate backwards. YORK INTERNATIONAL...
FORM 201.18-NM2 29119A SIDE VIEW 29121A 29121A TOP VIEW TOP VIEW DISPLAY SWITCH PUSHED TO LEFT INDICATES “ON” 29120A SIDE VIEW FIG. 39 – MOTOR PROTECTOR YORK INTERNATIONAL...
Remote Reset Curr = 105% FLA - {(4sec - 1 sec) X (75%FLA)} shown in Section 1.12. 10 sec Never bypass a flow switch. This will = 105% - 225%FLA sec 10 sec cause damage to the chiller and void any warranties. = 82.5% FLA YORK INTERNATIONAL...
Page 103
If an inductive device Reset Temp = 66°C sec (relay, contactor) is supplying these 10 sec contacts, the coil of the device must = 6ºC (12ºF) be suppressed with a standard RC sup- pressor (50Hz models) across the in- ductive coil. YORK INTERNATIONAL...
NOTE : Dimple is positioned at top edge Dip Switch Set (8 switches) S2 to S5 System Switches S2 = System 1 S3 = System 2 S4 = System 3 S5 = System 4 FIG. 40 – COMPONENT LAYOUT YORK INTERNATIONAL...
(150 ºF) and will turn on when the discharge temperature tem or if power is lost to the control panel. The internal is equal to or less than 66°C (150 ºF). contacts are normally open (N.O.) and will close when YORK INTERNATIONAL...
ON or OFF. cal equipment) and the alarm circuit should fail to function, YORK will not MANUAL Lead/Lag selection will be automatically be liable for damages. overridden by the micro to allow the lag compressor to automatically become the lead anytime the selected lead 1.20 RUN STATUS (CHILLER)
This message indicates that either an ISN or RCC (Re- amples of each display. In each example "#" is used as mote Control Center) has turned the unit OFF through applicable to represent the system number where mes- the RS-485 port. sages apply to individual systems. YORK INTERNATIONAL...
Section 7.4. This allows reprogram- out. The display shows the time before the respective ming of setpoints, cutouts, and compressor can start. This display will only appear af- ter the anti-recycle timers have timed out. schedule. YORK INTERNATIONAL...
Section 8.2 / Leaving Water Temperature Cutout, page 138). The chiller fault will clear when temperature Any time that a Unit Fault occurs, the shutdown will be rises 2°C (4ºF) above the cut-out and cooling demand logged into the HISTORY BUFFER. exists. YORK INTERNATIONAL...
3 For the first 4 seconds of operation discharge tempera- seconds. Automatic restart will occur after the first 2 shutdowns when the anti-recycle timer times out and ture is ignored. After 4 seconds of operation the com- YORK INTERNATIONAL...
Page 113
3.4 bar (50 PSID) or the tion pressure falls below the calculated cutout value system will be shut down. For lower ambients, the lin- before 225 seconds of run time, the system will be shut ear ramp times are as follows: down. YORK INTERNATIONAL...
From this time the system will programmable between 0.3 - 5 bar (5 - 70 PSIG) for R- be shut down if average motor current is less than 10% 22 and R407c models. In this mode, the cutout should of FLA. YORK INTERNATIONAL...
The Display keys and the data available from each is as ture, discharge superheat and compressor slide valve follows: position. 3.2 CHILLED LIQUID TEMPS KEY Examples of these displays are as follows where # is When the Chilled Liquid Temperatures key is pressed, the appropriate system number : YORK INTERNATIONAL...
This display shows the average motor current in amps 0 -40. and average compressor motor current as a percentage of FLA. All values are approximate. Keep in mind that Superheats are the difference between the respective current in “amps” is an “approximate” value. YORK INTERNATIONAL...
At the end of the sequence, above -4°C (25ºF) can be used to automatically shut the display will automatically revert to the first Option down the chiller when direct cooling methods become Switch message. operational. YORK INTERNATIONAL...
After scrolling through the data, the display returns to the status message. The following keys can be scrolled using the Function Key: Chilled Liquid Temps, System # Data, Motor Current and Options. YORK INTERNATIONAL...
“rate control” ted from the microprocessor to the remote printer. As and “temperature deviation from setpoint” to determine the data is transmitted it is erased from the memory. when loading should occur. YORK INTERNATIONAL...
Page 121
PWM TEMP – EMS PWM Temp. Reset Enabled tem. Both systems have their own control panel, but only the System 1 and 2 panel is fitted with a keypad CUR/TEMP – EMS PWM Current Limiting & Temperature Reset Enabled and display. YORK INTERNATIONAL...
SUCTION SUPERHEAT 11.2 ºF for the appropriate number of systems: SAT DISCHARGE TEMP 112.1 ºF DISCHARGE SUPERHEAT 33.4 ºF YORK INTERNATIONAL CORPORATION SLIDE VALVE STEP MILLENNIUM SCREW CHILLER COOLER INLET REFRIG 23.6 ºF LIQUID LINE SOLENOID ECONOMIZER TXV SOLENOID UNIT STATUS...
This message displays the suction pressure cut-out pro- grammed at the time of the fault. S H U T D O W N O C C U R R E D 5 : 5 9 A M N O V YORK INTERNATIONAL...
Page 124
A mixed water sensor may be system was ON or OFF at the time of the fault. present when multi-unit sequencing is utilized. If no mixed water temperature sensor is installed, the display will not appear. YORK INTERNATIONAL...
Page 125
One section contains numbers 1 and 2 refrigerant 407C mode, indicates the refrigerant temperature at the systems and the associated evaporator. The second sec- inlet of the cooler. tion contains number 3 and 4 refrigerant systems and YORK INTERNATIONAL...
“AM” or “PM” on the display. For â â â â â this is not done, the new values entered will be lost and example, pressing the key when the cursor is on “PM” the original values will be returned. changes it to “AM”. YORK INTERNATIONAL...
7ºC Temp. RANGE operating 6.2 CHILLED LIQUID TEMPERATURE CONTROL (44.0ºF) range) The Setpoints keys are used to program the required chilled water liquid temperature for the application. This 6ºC (42.0ºF) is accomplished by programming the "Setpoint" and the YORK INTERNATIONAL...
Page 129
At this point the compressors will be alternately loaded with loading Zero Unload Hold Load always occuring on the compressor with the lowest slide Positive Hold Load Load valve step until the leaving chilled liquid is satisfied. YORK INTERNATIONAL...
Page 130
10 steps between system 1 and 2. It could only below the low limit of the Control Range. YORK INTERNATIONAL...
After the Setpoint and Range is keyed in, press the application, remembering to use a leading "0" for values ENTER Key to store the data in memory. less than 10ºC (or 10ºF). Press the ENTER Key to store the new value in memory. YORK INTERNATIONAL...
AM/PM designation. If stop schedule, as shown below, can be displayed using á á á á á â â â â â necessary press the key to change to the oppo- the Set Schedule / Holiday key: site time period. YORK INTERNATIONAL...
Page 133
Cancel. This will clear the programmed ULE will not affect on the holiday (*) “Holiday” days (the “0” key will not cancel out a “ * ” schedule. and cannot be used for correcting a programming error). YORK INTERNATIONAL...
If a power failure should again occur, the above process will again need to M A N U A L be repeated to bring the chiller back O V E R R I D E on line. See also Section 2.5. YORK INTERNATIONAL...
Failure to prop- desired language. erly program these values may cause damage to the Chiller or operating Pressing the Enter key repeatedly allows scrolling problems. through the programmable displays. YORK INTERNATIONAL...
Typically the unload point should be set 1.4 to 1.7 bar (20 - 25 PSIG) below the below the discharge pressure 100 – 60 New Cutout = 3 = 1.2 bar (17.6PSIG) cutout setting. The micro will accept a range of pro- YORK INTERNATIONAL...
Page 137
-17ºC (1ºF) for more than programmable value is password protected. a short time. To program the High Ambient Cutout, key in the re- quired setting and press the Enter key to store the value into memory and scroll to the next display. YORK INTERNATIONAL...
Page 138
If the programmable limit is set between 100% and 105% reduce cycling and maximize motor life. 600 seconds of full load current, this safety will protect against ex- is recommended. YORK INTERNATIONAL...
This will preset all programmable values the system. Details of manual and automatic lead / lag under the Program key to values that will allow opera- operation are outlined in Section 1.21. YORK INTERNATIONAL...
Page 140
Low Amb. -4ºC 25°F High Ambient Temperature Cut-Out 38ºC 130°F Discharge Pressure Unload 26 bar 375PSIG High Motor Current Unload 100% Anti-Recycle Timer 600 sec. Leaving Chilled Liquid Temp Cut-Out 2ºC 36°F Suction Pressure Cut-Out 3 bar 44PSIG YORK INTERNATIONAL...
<15.2 BAR & <29.4ºC 15M, 16M, 17M, 18M, 19M 230, 231, 232 10, 14, 15 TABLE 3 – CONDENSER FAN CONTROL & FAN CONTACTOR DATA FOR DXST UNITS WITH 5 FANS/SYSTEM FIGURE 44 – CONDENSER FAN LAYOUT FOR DXST 2-COMPRESSOR UNITS YORK INTERNATIONAL...
Compressor Oil Level improper maintenance during the warranty period, Check the compressor oil level after the compressor YORK shall not be liable for costs incurred to return has been operating on ‘FULL LOAD’ for approximately the unit to satisfactory condition.
YORK Order No. ________________________ CHILLER/COMPRESSOR Compr. Ser. No. _________________________ Operating Log Unit Ser. No. ___________________________ Refrigerant _____________________________ Date Time Hour Meter Reading Equipment Room Temp./Outdoor Temp. Suction Pressure Suction Temperature Suction Superheat Discharge Pressure Actual Discharge Temperature Oil Pressure Oil Temperature...
* Reserved for customer use for any special site determined requirements. This procedure must be performed at the specified time interval by an Industry Certified Technician who has been trained and qualified to work on this type of YORK equipment. A record of this procedure being successfully carried out must be maintained on file by the equipment owner should proof of adequate maintenance be...
Full unit model number, serial number, application and details of the parts required. All requests for parts should be made to your local YORK Sales and Service Center. RECOMMENDED COMPRESSOR OILS The correct type of oil must be used in the unit as shown on the unit data plate and labels.
Check that the compressor unloads correctly. Measured temperature is incorrect. Check sensor calibration, location and wiring. Chiller FAULT: VAC Check mains supply is stable and within allowable UNDERVOLTAGE Poor mains supply voltage. limits. displayed. Check for voltage dip on compressor start. YORK INTERNATIONAL...
Page 148
Check operation of economizer and motor cooling TEV’s and liquid solenoid valve. SYS # CURR LIMITING High compressor motor current has Check if liquid temperature is within operating limits. displayed activated unloading. Check if ambient air temperature is above operating (Compressor current limits. unloading.) YORK INTERNATIONAL...
Test Point ............Micro-board J11-9/3 System 1: ............Micro-board J13-7/1 System 2: ............Micro-board J14-7/1 Oil Pressure: System 1: ............Micro-board J13-8/3 System 2: ............Micro-board J14-8/3 Discharge Pressure: System 1: ............Micro-board J15-8/3 System 2: ............Micro-board J15-7/1 YORK INTERNATIONAL...
BUYER’S SOLE AND EXCLUSIVE REMEDY IN Except for reciprocating replacement compressors, which THE EVENT OF A DEFECT IN WORKMANSHIP YORK warrants for a period of one year from date of OR MATERIALS. IN NO EVENT SHALL YORK’S shipment, YORK warrants reconditioned or replacement...
Need help?
Do you have a question about the MILLENNIUM YCAS and is the answer not in the manual?
Questions and answers