Remote Output Signal - Mitsubishi Electric NZ2GF2S-60MD4 User Manual

Cc-link ie field network multiple input (voltage/current/temperature) module
Table of Contents

Advertisement

Remote output signal

Initial data setting request flag
■Device number
Name
Initial data setting request flag
■Description
Turn on Initial data setting request flag (RY9) after writing parameter data to the remote buffer memory in the program.
Once the change in operating conditions is completed, Initial data setting completion flag (RX9) turns on.
For the timing of turning the flag on and off, refer to the following.
• Initial data setting completion flag (RX9) (Page 107 Initial data setting completion flag)
Error clear request flag
■Device number
Name
Error clear request flag
■Description
Error clear request flag (RYA) is used to clear Error flag (RXA), Disconnection detection signal (RX1B), Input signal error
detection signal (RX1C), Latest error code (RWr0), or Latest warning code (RWr1).
■When a moderate error, disconnection detection, or input signal error detection occurs
When Error clear request flag (RYA) is turned on and off after the cause of the error is eliminated, the error state is cleared
and Error flag (RXA) turns off.
If Error clear request flag (RYA) is turned off before Error flag (RXA) turns off, Error flag (RXA) does not turn off.
For the timing of turning the flag on and off, refer to the following.
• Error flag (RXA) (Page 108 Error flag)
• Disconnection detection signal (RX1B) (Page 109 Disconnection detection signal)
• Input signal error detection signal (RX1C) (Page 111 Input signal error detection signal)
■When a major error occurs
Error flag (RXA) does not turn off even if Error clear request flag (RYA) is turned on and off.
For the timing of turning the flag on and off, refer to the following.
• Error flag (RXA) (Page 108 Error flag)
Device number
RY9
Device number
RYA
Appendix 1 Details of Remote I/O Signals
A
APPENDICES
113

Advertisement

Table of Contents
loading

Table of Contents