Changing the parameter without changing the network
configuration
To change only the created module parameter of the slave station without changing the network configuration, set the
parameter in the following procedure.
1.
Open the CC IE Field configuration window.
For the master/local module QJ71GF11-T2
Project window  [Parameter]  [Network Parameter]  [Ethernet / CC IE / MELSECNET]  [CC IE Field
Configuration Setting] button
2.
Select the multiple input module in "List of stations" (1) on the CC IE Field configuration window.
3.
Open the "Parameter Processing of Slave Station" window.
[CC IE Field Configuration]  [Online]  [Parameter Processing of Slave Station]
4.
Set "Method selection" to "Parameter read".
5.
Click the [Execute] button and the following window is displayed.
6.
Click the [Yes] button.
7.
The parameter is read from the multiple input module.
6 VARIOUS SETTINGS
56
6.2 Changing the Parameter