■Allowable difference of type T thermocouple
Measured temperature
Between -40 and 125 (125 not included)
Between 125 and 350 (350 not included)
Between -40 and 133 (133 not included)
Between 133 and 350 (350 not included)
Between -67 and 40 (40 not included)
Between -200 and -67 (-67 not included)
■Allowable difference of type J thermocouple
Measured temperature
Between -40 and 375 (375 not included)
Between 375 and 750 (750 not included)
Between -40 and 333 (333 not included)
Between 333 and 750 (750 not included)
■Allowable difference of type K thermocouple
Measured temperature
Between -40 and 375 (375 not included)
Between 375 and 1000 (1000 not included)
Between -40 and 333 (333 not included)
Between 333 and 1200 (1200 not included)
Between -167 and 40 (40 not included)
Between -200 and -167 (-167 not included)
Class
Class 1
Class 2
Class 3
Class
Class 1
Class 2
Class
Class 1
Class 2
Class 3
Allowable difference
0.5
0.4% of the measured temperature
1.0
0.75% of the measured temperature
1.0
1.5% of the measured temperature
Allowable difference
1.5
0.4% of the measured temperature
2.5
0.75% of the measured temperature
Allowable difference
1.5
0.4% of the measured temperature
2.5
0.75% of the measured temperature
2.5
1.5% of the measured temperature
APPENDICES