Mitsubishi Electric NZ2GF2S-60MD4 User Manual page 140

Cc-link ie field network multiple input (voltage/current/temperature) module
Table of Contents

Advertisement

EMC Directive related standards
■Emission requirements
Specifications
EN61131-2: 2007
*1 QP: Quasi-peak value, Mean: Average value
*2 The module is an open-type device (a device designed to be embedded in other equipment) and must be installed inside a conductive
control panel. The tests were conducted with the module installed in a control panel.
■Immunity requirements
Specifications
EN61131-2: 2007
*1 The module is an open-type device (a device designed to be embedded in other equipment) and must be installed inside a conductive
control panel. The tests were conducted with the module installed in a control panel.
*2 The accuracy of an analog-digital converter module may temporarily vary within 10%.
APPENDICES
138
Appendix 7 EMC and Low Voltage Directives
Test item
Test details
CISPR16-2-3
Radio waves from the product are
*2
Radiated emission
measured.
CISPR16-2-1,
Noise from the product to the power
CISPR16-1-2
line is measured.
*2
Conducted emission
Test item
Test details
EN61000-4-2
Immunity test in which electrostatic
Electrostatic discharge
is applied to the cabinet of the
*1
immunity
equipment.
EN61000-4-3
Immunity test in which electric fields
Radiated, radio-
are irradiated to the product
frequency
electromagnetic field
*1
immunity
EN61000-4-4
Immunity test in which burst noise is
Electrical first transient
applied to the power line and signal
*1
burst immunity
line
EN61000-4-5
Immunity test in which lightning
*1
Surge immunity
surge is applied to the power line
and signal line
EN61000-4-6
Immunity test in which high
Conducted RF
frequency noise is applied to the
*1
immunity
power line and signal line
EN61000-4-8
Immunity test in which the product
Power-frequency
is installed in inductive magnetic
magnetic field
field
*1
immunity
EN61000-4-11
Immunity test in which power supply
Voltage dips and
voltage is momentarily interrupted
*1
interruption immunity
Standard value
• 30M to 230MHz, QP: 40dBV/m (10m in measurement
*1
range)
• 230M to 1000MHz, QP: 47dBV/m (10m in measurement
range)
• 150k to 500kHz, QP: 79dB, Mean: 66dB
• 500k to 30MHz, QP: 73dB, Mean: 60dB
Standard value
• 8kV air discharge
• 4kV contact discharge
80% AM modulation@1kHz
• 80M to 1000MHz: 10V/m
• 1.4G to 2.0GHz: 3V/m
• 2.0G to 2.7GHz: 1V/m
• AC/DC main power, I/O power, AC I/O (unshielded): 2kV
• DC I/O, analog, communication cable: 1kV
• AC power line, AC I/O power, AC I/O (unshielded): 2kV CM,
1kV DM
• DC power line, DC I/O power: 0.5kV CM, DM
• DC I/O, AC I/O (shielded), analog
0.15M to 80MHz,
80% AM modulation @1kHz, 10Vrms
50Hz/60Hz, 30A/m
• Apply at 0%, 0.5 cycles and zero-cross point
• 0%, 250/300 cycles (50/60Hz)
• 40%, 10/12 cycles (50/60Hz)
• 70%, 25/30 cycles (50/60Hz)
*1
*2
, communication: 1kV CM

Advertisement

Table of Contents
loading