Mitsubishi Electric NZ2GF2S-60MD4 User Manual page 131

Cc-link ie field network multiple input (voltage/current/temperature) module
Table of Contents

Advertisement

Micro voltage input characteristic
The following figure and tables show the analog input range list at micro voltage input and a graph of the micro voltage input
characteristics.
(a)
digit
32767
32000
0
-32000
-32768
-200
-100
0
digit: Digital output value
mV: Analog input voltage [mV]
(a) Practical analog input range
Input range setting
Offset value
-100 to 100mV
0mV
*1 When an analog input exceeds the range of digital output values, the corresponding digital output value is fixed to the maximum or
minimum.
Input range setting
-100 to 100mV
• The application needs to be within the practical analog input range of each input range. If a value is out of
the range, the resolution and accuracy may not fall within the range of performance specifications. (Do not
use the values in the dotted line area in the above micro voltage input characteristics graph.)
• Do not input a voltage of 15V or higher/lower. This may damage the elements.
mV
100
200
Gain value
100mV
Digital output value
Minimum
-32768
*1
Digital output value
Resolution
-32000 to 32000
3.125V
Maximum
32767
Appendix 4 I/O Conversion Characteristic
A
APPENDICES
129