Conversion setting for disconnection detection
Conversion setting for disconnection detection (address: 010FH) can configure the values stored in CH Digital output value
(RWr2 to RWr5) and CH Digital output value (32 bits) (RWr10 to RWr17) upon disconnection detection. Thus, disconnection
detection is enabled only by checking CH Digital output value (RWr2 to RWr5) and CH Digital output value (32 bits)
(RWr10 to RWr17) without monitoring Disconnection detection signal (RX1B). The default value of Conversion setting for
disconnection detection (address: 010FH) is Down scale (1H). Change the setting value as needed.
Conversion setting for disconnection detection
Up scale (0H)
Down scale (1H)
Arbitrary value (2H)
Value immediately before disconnection (3H)
■Up scale and down scale
The up-scale value (upper limit value + 5% of the input range) and down-scale value (lower limit value - 5% of the input range)
of the input range currently set are stored in CH Digital output value (RWr2 to RWr5) and CH Digital output value (32 bits)
(RWr10 to RWr17) when a disconnection occurs.
Moreover, if the value of "upper limit value + 5% of the input range" is 32767 or more when up scale is selected, 32767 is
stored.
Whereas, if the value of "lower limit value - 5% of the input range" is -32768 or less when down scale is selected, -32768 is
stored.
• Micro voltage
Input range
-100 to 100mV
*1 When the value of "upper limit value + 5% of the input range" is 32767 or more
*2 When the value of "lower limit value - 5% of the input range" is -32768 or less
• Thermocouple
Input range
Type B thermocouple (0 to 1820)
Type R thermocouple (-50 to 1760)
Type S thermocouple (-50 to 1760)
Type K thermocouple (-270 to
1370)
Type E thermocouple (-270 to
1000)
Type J thermocouple (-210 to
1200)
Type T thermocouple (-270 to 400)
Type N thermocouple (-270 to
1300)
Type U thermocouple (-200 to 600)
Type L thermocouple (-200 to 900)
Type PL thermocouple (0 to
1390)
Type W5Re/W26Re thermocouple (0
to 2300)
Digital output value
Output range
-32000 to 32000
Digital process value ()
Temperature measuring range
0 to 1820
-50 to 1760
-50 to 1760
-270 to 1370
-270 to 1000
-210 to 1200
-270 to 400
-270 to 1300
-200 to 600
-200 to 900
0 to 1390
0 to 2300
Processing at disconnection detection
The up scale value (upper limit value + 5% of the input range) of the input
range currently set is stored in CH Digital output value (RWr2 to RWr5) and
CH Digital output value (32 bits) (RWr10 to RWr17).
The down scale value (lower limit value - 5% of the input range) of the input
range currently set is stored in CH Digital output value (RWr2 to RWr5) and
CH Digital output value (32 bits) (RWr10 to RWr17).
The value set in CH Conversion setting value for disconnection detection
(address: 0110H to 0117H) is stored in CH Digital output value (RWr2 to
RWr5) and CH Digital output value (32 bits) (RWr10 to RWr17).
The value immediately before a disconnection occurs is held in CH Digital
output value (RWr2 to RWr5) and CH Digital output value (32 bits) (RWr10
to RWr17).
Up scale
*1
32767
Up scale
1911.0
1850.5
1850.5
1452.0
1063.5
1270.5
433.5
1378.5
640.0
955.0
1459.5
2415.0
7.4 Disconnection Detection Function
Down scale
*2
-32768
Down scale
-91.0
-140.5
-140.5
-352.0
-333.5
-280.5
-303.5
-348.5
-240.0
-255.0
-69.5
-115.0
7 FUNCTIONS
7
65