Conversion setting for disconnection detection
Conversion setting for disconnection detection (address: 010FH) can configure the values stored in CH Digital output value
(RWr2 to RWr5) and CH Digital output value (32 bits) (RWr10 to RWr17) upon disconnection detection. Thus, disconnection
detection is enabled only by checking CH Digital output value (RWr2 to RWr5) and CH Digital output value (32 bits)
(RWr10 to RWr17) without monitoring Disconnection detection signal (RX1B). The default value of Conversion setting for
disconnection detection (address: 010FH) is Down scale (1H). Change the setting value as needed.
Conversion setting for disconnection detection
Up scale (0H)
Down scale (1H)
Arbitrary value (2H)
Value immediately before disconnection (3H)
■Up scale and down scale
The up-scale value (upper limit value + 5% of the input range) and down-scale value (lower limit value - 5% of the input range)
of the input range currently set are stored in CH Digital output value (RWr2 to RWr5) and CH Digital output value (32 bits)
(RWr10 to RWr17) when a disconnection occurs.
Moreover, if the value of "upper limit value + 5% of the input range" is 32767 or more when up scale is selected, 32767 is
stored.
Whereas, if the value of "lower limit value - 5% of the input range" is -32768 or less when down scale is selected, -32768 is
stored.
• Micro voltage
Input range
-100 to 100mV
*1 When the value of "upper limit value + 5% of the input range" is 32767 or more
*2 When the value of "lower limit value - 5% of the input range" is -32768 or less
• Thermocouple
Input range
Type B thermocouple (0 to 1820)
Type R thermocouple (-50 to 1760)
Type S thermocouple (-50 to 1760)
Type K thermocouple (-270 to
1370)
Type E thermocouple (-270 to
1000)
Type J thermocouple (-210 to
1200)
Type T thermocouple (-270 to 400)
Type N thermocouple (-270 to
1300)
Type U thermocouple (-200 to 600)
Type L thermocouple (-200 to 900)
Type PL thermocouple (0 to
1390)
Type W5Re/W26Re thermocouple (0
to 2300)
Digital output value
Output range
-32000 to 32000
Digital process value ()
Temperature measuring range
0 to 1820
-50 to 1760
-50 to 1760
-270 to 1370
-270 to 1000
-210 to 1200
-270 to 400
-270 to 1300
-200 to 600
-200 to 900
0 to 1390
0 to 2300
Processing at disconnection detection
The up scale value (upper limit value + 5% of the input range) of the input
range currently set is stored in CH Digital output value (RWr2 to RWr5) and
CH Digital output value (32 bits) (RWr10 to RWr17).
The down scale value (lower limit value - 5% of the input range) of the input
range currently set is stored in CH Digital output value (RWr2 to RWr5) and
CH Digital output value (32 bits) (RWr10 to RWr17).
The value set in CH Conversion setting value for disconnection detection
(address: 0110H to 0117H) is stored in CH Digital output value (RWr2 to
RWr5) and CH Digital output value (32 bits) (RWr10 to RWr17).
The value immediately before a disconnection occurs is held in CH Digital
output value (RWr2 to RWr5) and CH Digital output value (32 bits) (RWr10
to RWr17).
Up scale
*1
32767
Up scale
1911.0
1850.5
1850.5
1452.0
1063.5
1270.5
433.5
1378.5
640.0
955.0
1459.5
2415.0
7.4 Disconnection Detection Function
Down scale
*2
-32768
Down scale
-91.0
-140.5
-140.5
-352.0
-333.5
-280.5
-303.5
-348.5
-240.0
-255.0
-69.5
-115.0
7 FUNCTIONS
7