Parameter area initialization command
■Address
Name
Parameter area initialization command
■Description
Parameter area initialization command (address: 1002H) sets the parameters stored in a remote buffer memory and non-
volatile memory to the default value.
When Non-volatile memory data error (parameter) (error code: 0130H) occurs, the module can be recovered using this
command.
Parameter area initialization command
Not commanded
Commanded
■Operation of the parameter area initialization
When Parameter area initialization command (address: 1002H) is set to Commanded (1), the parameters stored in a non-
volatile memory are set to the default value.
Module operation information
error data
Parameter area initialization
Not commanded
command (address: 1002H)
(0)
Parameter area initialization
completed (address: 1003H)
Even if Parameter area initialization command (address: 1002H) is carried out, the following remote input
signals are not cleared.
• Warning flag (RX7)
• Error flag (RXA)
• Disconnection detection signal (RX1B)
• Input signal error detection signal (RX1C)
Following execution of Parameter area initialization command (address: 1002H), normal operation is carried
out by turning off and on the module power supply.
Controlled by the multiple input module
Controlled by the program
Module operation information
Commanded (1)
Not performed (0)
Address
1002H
Setting value
0H (default value)
1H
Default value
Not commanded (0)
Completed
Not performed (0)
(1)
Appendix 3 Details of Remote Buffer Memory Areas
A
APPENDICES
125