Control Mode; Io-Link Information - gefran GRM-H 15 Configuration And Programming Manual

Compact power controllers, analog command and io-link communication
Table of Contents

Advertisement

6.3.

CONTROL MODE

6.3.1.

IO-Link information

Port class
Baud rate
IO-Link version (1)
Profile
Process data input length
(14 byte)
Process data output length (2 byte)
Min cycle time
SIO mode
ISDU
Database
Compliant with IO-Link Interface Specification v.1.1.2 (July 2013)
(1)
A
COM2 (38.4 kbit/s)
1.1
Common profile
% power supplied: 2 bytes
Ld.A (load current): 2 bytes
Ld.V (load voltage): 2 bytes
Ld.P (load power): 2 bytes
Ld.I (load impedence): 2 bytes
STATUS2: 2 bytes
for diagnostics:
STATUS2_NO_CURRENT: 1 bit
STATUS2_NO_VOLTAGE: 1 bit
STATUS2_SSR_SHORT: 1 bit
STATUS2_HB: 1 bit
STATUS3: 2 bytes
for diagnostics:
STATUS3_DRYOUT: 1 bit
STATUS3_CURRENT_SENSOR_BROKEN: 1 bit
STATUS3_OVER_PEAK_CURRENT_PROJECTION:
1 bit
STATUS3_OVER_RMS_CURRENT: 1 bit
STATUS3_OVER_PEAK_CURRENT: 1 bit
STATUS3_SHORT_CIRCUIT_CURRENT: 1 bit
STATUS3_60HZ: 1 bit
STATUS3_FREQUENCY_WARNING: 1 bit
STATUS3_SOFTSTART_END: 1 bit
STATUS3_ SOFTSTART_ACTIVE: 1 bit
STATUS3_SCR_OVER_HEAT: 1 bit
STATUS3_SCR_TEMP_SENSOR_BROKEN: 1 bit
% Power to be supplied: 2 bytes
20ms
Supported
Supported
Supported
819XX_MAN_GRM-H_11-2022_ENG_pag. 77