5.6.1.

Soft start ramp settings

It can be enabled in either phase control or pulse train
mode and controls the conduction angle.
It is enabled through the PS.E. parameter
The soft start ramp, always in Phase Angle, starts
from a conduction angle and reaches 100.0% in a
time set in the PS.tm parameter from 0.1 to 60.0 s.

5.6.1.1. Soft start enabling

Acronym
PS.E
Soft start ramp enabling.
Options:
0
Ramp disabled
1
Ramp enabled (linear in angle)
2
Ramp enabled (linear in power)
3
Ramp enabled (for IR lamps)

5.6.1.2. Soft start ramp duration

Acronym
PS.tm
Phase soft start ramp duration.
min...max: 0.1 ... 60.0

5.6.1.3. Soft start ramp reactivation time

Acronym
PS.oF
The parameter sets the minimum non-operating time to reactivate the phase soft start ramp.
min...max: 0 ... 999 s
App / GF_eXpress menu
Power Control
App / GF_eXpress menu
Power Control
App / GF_eXpress menu
Power Control
819XX_MAN_GRM-H_11-2022_ENG_pag. 64
Soft start ends before the defined time if the power
reaches the corresponding required value set in
manual control or calculated by the analog input.
The soft start ramp triggers at first start up after
power-on. It can be reactivated automatically if the
OFF condition occurs for a time longer than that
which can be set in PS.oF (if = 0 the function is as if it
were disabled).
Attribute Retentive
Description
R/W
Attribute Retentive
Description
R/W
Attribute Retentive
Description
R/W
U.M.
Default
-
0
U.M.
Default
s
10.0
U.M.
Default
s
2