Extrarapid Fuses; Accessoires; Fans (For 90A/120A Models Only) - gefran GRM-H 15 Configuration And Programming Manual

Compact power controllers, analog command and io-link communication
Table of Contents

Advertisement

7.4.

Extrarapid fuses

Model
GRM-H 15
GRM-H 25/25I
GRM-H 30/30I
GRM-H 40
GRM-H 50
GRM-H 60, GRM-H 75
GRM-H 90
GRM-H 120
An electrical protection device known as a GG FUSE must be used to ensure protection against short-circuit of the electrical cable (see EN 60439-1,
paragraph 7.5 Short-circuit protection and short-circuit withstand strength" and 7.6 "Switching devices and components installed in ASSEMBLIES",
or the equivalent paragraphs of standard EN 61439-1).
7.5.

Accessoires

Code
Description
F089025
1 NFC dongle for configuration via App + 1 Gefran keychain lanyard
F089026
5 NFC dongles for configuration via App + 5 Gefran keychain lanyards
F089027
10 NFC dongles for configuration via App
F060800
Cable for programming with PC, USB-TTL 3 V with USB - microUSB connectors, length 1,8 m
7.6.

Fans (for 90A/120A models only)

Model
Code
90A FAN60
363484
120A FAN60 363011
90A FAN61
363485
120A FAN61 363003
FAN62
363037
FAN63
363037
PERIODIC CLEANING
Every 6-12 months (depending on dust in the place where it is installed), blow a jet of compressed air downward through the cooling heatsink
(on the opposite side of the fan).
In this way both the heat sink and the cooling fan are cleaned.
IN THE EVENT OF OVERTEMPERATURE ALARM
If periodic cleaning does not eliminate the problem, perform the following operations:
1. Disconnect the fan cables from the terminal block (if present) or disconnect the fan connector from the GRM-H (FAN63).
2. Unscrew the screws securing the fan to the support brackets
3. Check the condition of the fan, clean it or replace it
4. Reassemble the fan
Fuse manufacturer
Bussmann Div Cooper (UK) Ltd
Bussmann Div Cooper (UK) Ltd
Bussmann Div Cooper (UK) Ltd
Bussmann Div Cooper (UK) Ltd
Bussmann Div Cooper (UK) Ltd
Bussmann Div Cooper (UK) Ltd
Bussmann Div Cooper (UK) Ltd
Bussmann International Inc. USA
Type
230 Vac 60mm x 60mm x 30mm for 90A models
230Vac 80mm x 80mm x 38 mm for 120A models Separate power supply
115Vac 60mm x 60mm x 30 mm for 90A models
115Vac 80mm x 80mm x 38 mm for 120A models Separate power supply
24 Vdc 60mm x 60mm x 25mm
24 Vdc 60mm x 60mm x 25mm
819XX_MAN_GRM-H_11-2022_ENG_pag. 93
Fuse Model size
FWC16A10F 10x38
FWC25A10F 10x38
FWP40A14F 14x51
FWP40A14F 14x51
FWP63A22F 22x58
FWP80A22F 22x58
FWP100A22F 22x58
170M1418 000-TN/80
Supply
Separate power supply
Separate power supply
Separate power supply
Internally powered by GRM-H

Advertisement

Table of Contents
loading

Table of Contents