Enabling Hb Alarm; Enable Memory For Hb Alarm; Hb Alarm Functionb - gefran GRM-H 15 Configuration And Programming Manual

Compact power controllers, analog command and io-link communication
Table of Contents

Advertisement

Settings

5.2.1.3. Enabling HB alarm

Acronym
App / GF_eXpress menu
Hb.E
Enabling HB alarm.
Options:
0 Disabled
1 Enabled

5.2.1.4. Enable memory for HB alarm

Acronym
App / GF_eXpress menu
Hb.m
Enabling memory for HB alarm: after the causes that triggered the HB alarm have disappeared, the
alarm remains active until a reset is triggered by a key, serial line, IO-Link, or restarting the device.
Options:
0 Disabled
1 Enabled

5.2.1.5. HB alarm functionB

Acronym
App / GF_eXpress menu
Hb.F
HB alarm function.
Options:
Alarm triggered at a load current value lower than the set threshold (during con-
0
trol output ON period).
Alarm triggered at a load current value higher than the set threshold (during con-
1
trol output OFF period).
Alarm triggered if one of the two previous conditions persists (logical OR between
2
functions 0 and 1).
Alarms  HB alarm
Alarms  HB alarm
Alarms  HB Alarm
819XX_MAN_GRM-H_11-2022_ENG_pag. 37
Attribute Retentive
Description
R/W
Attribute Retentive
Description
R/W
Attribute Retentive
Description
R/W
U.M.
Default
-
1
U.M.
Default
-
0
U.M.
Default
-
0