Chapter 5 Function parameter
Parameter
No. Code
name
256.
Overcurrent
F8.00
stall gain
Overcurrent
257.
F8.01
stall protection
current
258.
Motor overload
F8.02
protection
selection
259.
Motor overload
F8.03
protection gain
Motor overload
260.
F8.04
pre-alarm
coefficient
261.
Overvoltage
F8.05
stall gain
Overvoltage
stall protection
262.
F8.06
voltage / energy
consumption
brake voltage
Input phase loss
263.
F8.07
protection
selection
264.
F8.08 Output phase
loss protection
selection
265.
Short to ground
F8.09
protection
Setting range
0 to 100
100% to 200%
0: Disable
1: Enable
0.20 to 10.00
50% to 100%
0 to 100
120% to 150%
Units digit:Input phase loss
protection selection
0: Disable
1: Enable
Tens digit:contactor
actuation protection
0: Disable
1: Enable
0: Disable
1: Enable
0: Invalid
1: Valid
58
Chan
Factory
Reference
ge
setting
page
20
150%
1
1.00
80%
0
130%
11
1
1
140
140
141
141
141
141
141
142
142
142

Hide quick links: