Powtran PI9100 Series Manual page 141

Table of Contents

Advertisement

Chapter 5 Function parameter
Output
Output
Frequency
Frequency
Set frequency
reaches detection
The inverter's multifunction output DO will output ON signal when the inverter's
operating frequency is in a certain range of target frequency
This parameter is used to set the frequency arrival detection range, the parameter is the
percentage of maximum frequency. The above figure is the schematic diagram of frequency
arrival.
Frequency detection value
F7.26
(FDT2)
Frequency detection
F7.27
hysteresis value (FDT2)
The frequency detection function is same as FDT1 exactly, please refer to the
instructions of FDT1 or function codes F7.23, F7.24.
Random arrivals frequency
F7.28
detection value 1
Random arrivals frequency
F7.29
detection width 1
Random arrivals frequency
F7.30
detection value 2
Random arrivals frequency
F7.31
detection width 2
输出频率 Hz
设定频率
频率到达
Frequency
检测信号
signal
ON
频率到达检出幅值示意图
Schematic diagram of frequency arrival detection amplitude
Detection amplitude
检出幅值
ON
0.00Hz
to
F0.19
(maximum frequency)
0.0% to 100.0% (FDT2
level)
0.00Hz
to
F0.19
(maximum frequency)
0.00%
to
100.0%
(maximum frequency)
0.00Hz
to
F0.19
(maximum frequency)
0.00%
to
100.0%
(maximum frequency)
136
time t
time t
50.00Hz
5.0%
50.00Hz
0.0%
50.00Hz
0.0%

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents