Chapter 7 Troubleshooting

PI9000 can provide effective protection when the equipment performance is played
fully. The following faults may appear in the process of use, please refer to the
following table to analyze the possible causes and then trouble shoot.
In case of damage to the equipment and the reasons that can not solved, please
contact with your local dealers/agents, or directly contact with the manufacturers to seek
solutions.

7.1 Fault alarm and countermeasures

PI9000 can provide effective protection when the equipment performance is played
fully. In case of abnormal fault, the protection function will be invoked, the inverter
will stop output, and the faulty relay contact of the inverter will start, and the fault
code will be displayed on the display panel of the inverter. Before consulting the
service department, user can perform self-check , analyze the fault cause and find out
the solution according to the instructions of this chapter. If the fault is caused by the
reasons as described in the dotted frame, please consult the agents of inverter or
directly contact with our company.
No. Fault ID
Failure type
Inverter unit
1
Err.01
protection
Acceleration
2
Err.02
overcurrent
Possible causes
1.the short circuit of inverter
output happens
2.the wiring for the motor
and the inverter is too long
3.module overheating
4.the internal wiring of
inverter is loose
5.the main control panel is
abnormal
6.the drive panel is abnormal.
7.the inverter module is
abnormal
1.the acceleration time is too
short
2.manual torque boost or V/F
curve is not suitable
3.the voltage is low
4.the short-circuit or earthing
of inverter output happens
5.the control mode is vector
and without identification of
parameters
185
Chapter 7 Troubleshooting
Solutions
1.eliminate peripheral
faults
2.additionally install the
reactor or the output filter
3.check the air duct is
blocked or not and the fan
is working normally or
not, and eliminate
problems
4.correctly plug all cables
5.seek for technical
support
1.increase acceleration
time
2.adjust manual torque
boost or V/F curve
3.set the voltage to the
normal range
4.eliminate peripheral
faults
5.perform identification
for the motor parameters