F7.12
Acceleration time 4
F7.13
Deceleration time 4
PI9000 provides 4 groups of deceleration time, respectively F0.13\F0.14 and the above
3 groups of deceleration time.
The 4 groups of deceleration time are defined exactly the same, please refer to the
instructions of F0.13 and F0.14. The 4 groups of deceleration time can be switched through
different combinations of the multi-function digital input terminal DI, please refer to the
instructions of function code F1.00 to F1.07 in the attachment 2 for the detailed application
methods .
Switching frequency point
F7.14
between acceleration time 1
and acceleration time 2
Switching frequency point
F7.15
between deceleration time 1
and deceleration time 2
The function is active when motor 1 is selected and DI terminal is not selected to switch
between ac/deceleration. It is used to automatically select ac/deceleration time by not DI
terminal but the operating frequency range when the inverter is running.
输出频率 Hz
Output
Frequency
Set frequency
F7.15
F7.14
Acceleration
time 2
Schematic diagram of switching between acceleration and deceleration
For the above figure in the process of acceleration, if the operating frequency is less
than F7.14, select acceleration time 1; otherwise select acceleration time 2.
For the above figure in the process of deceleration, if the operating frequency is more
than F7.15, select deceleration time 1; otherwise select deceleration time 2.
Forward/reverse
F7.16
deadband
It is the waiting time that the inverter reaches zero speed when the parameter is used to
switch between forward and reverse rotation.
加速时间 2
Acceleration
Time1
time 1
加减速时间切换示意图
rotation
Chapter 5 Function parameter
0.0s to 6500.0s
0.0s to 6500.0s
0.00Hz
F0.19(maximum
frequency)
0.00Hz
F0.19(maximum
frequency)
deceleration
deceleration
time1
time 2
0.00s to 3600.0s
133
-
-
to
0.00Hz
to
0.00Hz
Deceleration time 2
0.0s