[ENG] 10.4. [DKSF 48.5 IU] How Can I Configure The Pinger in the Logic Module?

In order to configure the pinger you have to open the "
In the "PINGER" section, you can configure the network accessibility of the specified address. The result of the check (pinger status) can be
selected as the "input" of the logic rule. You can find out how to configure a rule in the "LOGIC" module by studying the section
[DKSF 48.5 IU] How Can I Use the "LOGIC" Module?
application of a pinger is automatic power-up of backup equipment in case of connection line failure.
where:
Address—IP address of the device which is checked for availability. An empty line disables the poll. 
Polling Period, s (5–900) — the value is selected according to the speed of detecting the fault.  Please also note that overly frequent power
switching can reduce equipment service life.If there is no ICMP response, echo (ping) is repeated after the timeout is completed, and not when
the next polling period occurs. 
Ping Timeout, ms (100-10000) — is ping response timeout. The timeout is selected for the reasons of typical device response speed, taking into
account network delays. If there is no response to ping after a timeout, the ping is repeated immediately. If after five periods of sending there is no
response, the status of the pinger changes to "
Status 
— possible values: «
  No reply
the pinger do not create any commands and their outputs are controlled by the other rules ot save the previous state. The pinger status is updated
automatically about four times a minute.  
If you use domain names, you should take into accont that due to the unavailability of the DNS server or the lack of an IP address in the
settings, the "
LOGIС
status.
 After configuration of the pinger values you should press the "
 After pinger configuration you have to set up the rule in the "
Can I Use the "LOGIC" Module?
Copyright © NetPing east Co., Ltd / E-mail:
LOGIC
 You can configure no more than two pingers -
In Default
: 15. 
silent
", and retries stop until the next verification period. 
», «
Silent
», « ». If the poll is not completed, the status can be unidentified.  In this case rules that depend on
-
" DNS module will not be able to determine the availability of the polled address. "
support@netpingdevice.com www.netpingdevice.com
" page of the device`s web interface: 
Apply Changes
" button. 
LOGIC
" module. How to do it, learn this section: 
/
[ENG] 10.2.
"PINGER
1",
"PINGER
2". A typical
In Default
: empty line.
In Default
: 1000.
Pinger
" changes into the "silent"
[ENG] 10.2. [DKSF 48.5 IU] How