NetPing 8/PWR-220 v4/SMS User Manual
Hide thumbs Also See for 8/PWR-220 v4/SMS:
Table of Contents

Advertisement

Quick Links

1. [Docs] NetPing 8/PWR-220 v4/SMS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
1.1 [ENG] NetPing 8/PWR-220 v4/SMS, User guide . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
1.1.1 [8PWR] Copyright and Disclaimer . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
1.1.2 [8PWR] Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
1.1.4 [8PWR] Sockets and Indication Elements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
1.1.5 [8PWR] Power Supply Channels Management . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
1.1.6 [8PWR] Setting Parameters to Default Values (to the Factory Settings) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
1.1.7 [8PWR] Using IO Lines for External Devices Management (in an Output Mode) . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
1.1.8 [8PWR] Sensors Plugin . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
1.1.9 [8PWR] Shipping Kit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
1.1.10 [8PWR] Operating and Storage Conditions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
1.1.11 [8PWR] Warranty . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
1.2 [ENG] NetPing 8/PWR-220 v4/SMS, Firmware description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
1.2.1 [ENG] 1. [DKSF 48.5 IU] The Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
1.2.2 [ENG] 2. [DKSF 48.5 IU] Getting Basic Information about The Device . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
1.2.2.1 [ENG] 2.1. [DKSF 48.5 IU] The Username and Password in Default . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
1.2.3 [ENG] 3. [DKSF 48.5 IU] Basic Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
1.2.3.3 [ENG] 3.3. [DKSF 48.5 IU] Changing a Username and a Password . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
1.2.3.5 [ENG] 3.5. [DKSF 48.5 IU] How to Restrict the Access to the Device? . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
1.2.3.6 [ENG] 3.6. [DKSF 48.5 IU] How to Turn Off All Notifications Quickly? . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
1.2.3.8 [ENG] 3.8. [DKSF 48.5 IU] How to Set up The Clock? . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
1.2.3.9 [ENG] 3.9. [DKSF 48.5 IU] I Want to Configure SYSLOG. How Can I do It? . . . . . . . . . . . . . . . . . . . . . . . . . 41
1.2.3.11 [ENG] 3.11. [DKSF 48.5 IU] How to Update the Firmware of the Device? . . . . . . . . . . . . . . . . . . . . . . . . . . 43
1.2.3.12 [ENG] 3.12. [DKSF 48.5 IU] What Messages are There in the System Log? . . . . . . . . . . . . . . . . . . . . . . . . 44
1.2.4 [ENG] 4. [DKSF 48.5 IU] Working with Temperature Sensors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48
1.2.4.3 [ENG] 4.3. [DKSF 48.5 IU] Where to See the Current Temperature? . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51
53
Sensor is changed. How to Do This? . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 54
1.2.5 [ENG] 5. [DKSF 48.5 IU] Working with a Humidity Sensor. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55
1.2.5.3 [ENG] 5.3. [DKSF 48.5 IU] Initial Configuration of a Humidity Sensor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 58
1.2.5.4 [ENG] 5.4. [DKSF 48.5 IU] Viewing Readings and Configuring Parameters of the Humidity Sensor in a Web
Interface . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 59
Changed. How Can I Do It? . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 60
1.2.6 [ENG] 6. [DKSF 48.5 IU] Working with 1W Smoke Sensors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 62
1.2.6.3 [ENG] 6.3. [DKSF 48.5 IU] Initial Configuration of Smoke Sensors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 65
changed. How To Do This? . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 69
changed. How to Do This? . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 75
for? . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 77
1.2.8 [ENG] 8. [DKSF 48.5 IU] Working with a Built-In Relay . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 78
1.2.8.1 [ENG] 8.1 [DKSF 48.5 IU] The Control Switch of the Relay . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 79
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
. . . . . . . . . . . . . . . . . . 66
. . . . . . . . . . . . . . . . . . 67
. . . . . . . . . . . . . . . . . . . . . . . . . 70
. . . . . . . . . . . . . . . . . . 72
53

Advertisement

Table of Contents
loading

Summary of Contents for NetPing 8/PWR-220 v4/SMS

  • Page 1: Table Of Contents

    1.2 [ENG] NetPing 8/PWR-220 v4/SMS, Firmware description ........
  • Page 2 1.2.8.1 [ENG] 8.1 [DKSF 48.5 IU] The Control Switch of the Relay ........79 1.2.8.2 [ENG] 8.2 [DKSF 48.5 IU] I Want to Configure the Sending of Notifications for Events About the Operation of the Relay.
  • Page 3: Docs] Netping 8/Pwr-220 V4/Sms

    NetPing server room environmental monitoring solutions and IP power distribution units. [Docs] NetPing 8/PWR-220 v4/SMS Copyright © NetPing east Co., Ltd / E-mail: support@netpingdevice.com www.netpingdevice.com / Phone: +886-2-23121582...
  • Page 4: Eng] Netping 8/Pwr-220 V4/Sms, User Guide

    NetPing server room environmental monitoring solutions and IP power distribution units. [ENG] NetPing 8/PWR-220 v4/SMS, User guide Copyright © NetPing east Co., Ltd / E-mail: support@netpingdevice.com www.netpingdevice.com / Phone: +886-2-23121582...
  • Page 5: 8Pwr] Copyright And Disclaimer

    User Guide, as well as firmware and software of devices and this User Guide belong to NetPing global Ltd. Сopying, replication and translation of this user guide to other languages are not allowed without a prior written permission of a rightholder.
  • Page 6: 8Pwr] Introduction

    NetPing server room environmental monitoring solutions and IP power distribution units. [8PWR] Introduction This user guide helps to become familiar with an operation of a  Netping 8/PWR-220 v3/SMS  device and get an idea about its functionality and technical specifications as well as prepare a device for an operation.
  • Page 7: 8Pwr] Device Overview

    A device is designed in standard dimensions for installation in a 19' rack. A height of a device is 1U. Inputs and output power supply channels are on a front and back panels of a device. Fasteners for mounting in a rack ("ears") can be bolted to NetPing 8/PWRv3/SMS both front and back, which gives a possibility to mount a device in a rack by any side.
  • Page 8: 8Pwr] Sockets And Indication Elements

    Ethernet 10/100 BASE-T port. A device has two such ports: one on a front panel and another one on a back panel. Together they form a dual port Ethernet-switch. One port is used for a network connection, another one is used for additional equipment connection (another NetPing device, administrator's laptop, etc.), which gives an opportunity to avoid installing of an additional switch on a remote site.
  • Page 9 NetPing server room environmental monitoring solutions and IP power distribution units. Power Supply Channels Status Indication On a front panel there are LEDs that indicate a status of the second group of power supply channels. Channels 5 - 8 are included into this group.
  • Page 10 NetPing server room environmental monitoring solutions and IP power distribution units. Power Supply Inputs On a front panel there is a power supply input B. On a back panel there is a power supply input A. Sensor Plugin Terminals On a back panel there is a terminal block for sensors plugin. Assignment of the terminals is from left to right: IO1, IO2, IO3, IO4, SC, SD, +5V, GND.
  • Page 11 NetPing server room environmental monitoring solutions and IP power distribution units. A  Reset button is located on a back panel of a device. It is designed to reset settings to default values. To reset settings, press the button Reset  w ith a sharp object and hold it while turning on a device.
  • Page 12: 8Pwr] Power Supply Channels Management

    Connecting a Load to Output Channels When connecting a load to output power supply channels there is a need to take into account capacity limits of a NetPing 8/PWRv3/SMS device. A maximum capacity of each channel separately is 1500 Watts. A maximum total capacity of four channels in one group is 1725 Watts. I.e., if a consumer with a maximum capacity of 1500 Watts is connected to a channel 1, then it is possible to connect a total load no more than 225 Watts...
  • Page 13: 8Pwr] Setting Parameters To Default Values (To The Factory Settings)

    NetPing server room environmental monitoring solutions and IP power distribution units. [8PWR] Setting Parameters to Default Values (to the Factory Settings) Resetting parameters to the factory settings is necessary in the following cases : A loss of a login and/or password to a web interface of a device;...
  • Page 14: 8Pwr] Using Io Lines For External Devices Management (In An Output Mode)

    BM8070D a power relay 16А/250V for DIN-rail (check out the compatibility of this relay with the NetPing device model on the relay web page on the site MP701 a power module switch (4 independent channels, 2 kW 10A each)
  • Page 15 NetPing server room environmental monitoring solutions and IP power distribution units. Copyright © NetPing east Co., Ltd / E-mail: support@netpingdevice.com www.netpingdevice.com / Phone: +886-2-23121582...
  • Page 16: 8Pwr] Sensors Plugin

    NetPing server room environmental monitoring solutions and IP power distribution units. [8PWR] Sensors Plugin Sensors 1-Wire Sensors 1-Wire ( Temperature 1-wire, (THS), 2m  and  Humidity sensor 1-wire ) connected to the connectors 1W plugs RJ12, allowed to use extension cords or splitters. Maximum cable length 1-Wire network is limited to 50 meters.
  • Page 17 Plugging NetPing AC/DIN Sockets When plugging a socket to a device, all wires are used except for a brown one. There is a need to switch an IO line, to which a NetPing AC/DIN socket is connected, to the status "output". When a status of an IO line is logic 0, the socket will have 220V, and a load will be turned on. When a status of an IO line is logic 1, a socket will be cut off power, and a load will be turned off.
  • Page 18: 8Pwr] Shipping Kit

    NetPing server room environmental monitoring solutions and IP power distribution units. [8PWR] Shipping Kit A shipping kit is shown at the picture: A shipping kit includes: A device NetPing 8/PWRv3/SMS; An antenna; A user guide; A packing box; A power cord – 2 pcs.;...
  • Page 19: 8Pwr] Operating And Storage Conditions

    NetPing server room environmental monitoring solutions and IP power distribution units. [8PWR] Operating and Storage Conditions A device is designed for continuous round the clock operation indoors. In operating conditions of use, a device is resistant to an environment with temperature in a range of 0°С...
  • Page 20: 8Pwr] Warranty

    NetPing server room environmental monitoring solutions and IP power distribution units. [8PWR] Warranty The manufacturer guarantees normal operation of the product within 24 months from the date specified on the warranty sticker if a buyer follows operating and storage conditions. Manufacturer warranty applies only to failure of a device which occurred because of defects in manufacturing process of products and components used.
  • Page 21: Eng] Netping 8/Pwr-220 V4/Sms, Firmware Description

    NetPing server room environmental monitoring solutions and IP power distribution units. [ENG] NetPing 8/PWR-220 v4/SMS, Firmware description Copyright © NetPing east Co., Ltd / E-mail: support@netpingdevice.com www.netpingdevice.com / Phone: +886-2-23121582...
  • Page 22: Eng] 1. [Dksf 48.5 Iu] The Introduction

    User Guide, as well as firmware and software of devices and this User Guide belong to NetPing global Ltd. Сopying, replication and translation of this user guide to other languages are not allowed without a prior written permission of a rightholder.
  • Page 23: Eng] 2. [Dksf 48.5 Iu] Getting Basic Information About The Device

    NetPing server room environmental monitoring solutions and IP power distribution units. [ENG] 2. [DKSF 48.5 IU] Getting Basic Information about The Device Copyright © NetPing east Co., Ltd / E-mail: support@netpingdevice.com www.netpingdevice.com / Phone: +886-2-23121582...
  • Page 24: Eng] 2.1. [Dksf 48.5 Iu] The Username And Password In Default

    NetPing server room environmental monitoring solutions and IP power distribution units. [ENG] 2.1. [DKSF 48.5 IU] The Username and Password in Default The username and the password for connecting to the device web-interface in default: Login: visor Password: ping This information is written on the device case: Copyright ©...
  • Page 25: Eng] 2.2. [Dksf 48.5 Iu] How To Know A Ip Address In Default And A Mac Address Of The Device

    NetPing server room environmental monitoring solutions and IP power distribution units. [ENG] 2.2. [DKSF 48.5 IU] How to Know a IP Address in Default and a MAC Address of the Device The IP address in default is written on the case of the device: The MAC address of the device you can see on the "HOME"...
  • Page 26 NetPing server room environmental monitoring solutions and IP power distribution units. Copyright © NetPing east Co., Ltd / E-mail: support@netpingdevice.com www.netpingdevice.com / Phone: +886-2-23121582...
  • Page 27: Eng] 2.3. [Dksf 48.5 Iu] Connecting To The Web-Interface Of A Device With Authentication In Default

    NetPing server room environmental monitoring solutions and IP power distribution units. [ENG] 2.3. [DKSF 48.5 IU] Connecting to The Web-Interface of a Device with Authentication in Default Web Interface A web interface is used to manage a device. To connect to a device and configure its parameters, there is a need to enter and IP address of a device in the address bar of a browser: ...
  • Page 28: Eng] 2.4. [Dksf 48.5 Iu] I Need To Know The Firmware And Hardware Versions, The Serial Number, The Device Model And Uptime. How Can I Do It

    NetPing server room environmental monitoring solutions and IP power distribution units. [ENG] 2.4. [DKSF 48.5 IU] I Need to Know the Firmware and Hardware Versions, the Serial Number, the Device Model and Uptime. How Can I Do It?  The information about the serial number, the device model, the firmware version, the hardware version  and the uptime you can find on the "HOME"...
  • Page 29: Eng] 2.5. [Dksf 48.5 Iu] Where Can I See The Hostname, The Location And The Contacts Of The Device

    Hostname is displayed on the "HOME" page and in the heading of the web interface, it is sent in Syslog messages and is accessible via SNMP - OID "sysName". Location — is the description of the installation location of the NetPing device. It is displayed on the "HOME" page and in the heading of the web interface, it is available via SNMP - OID "sysLocation".
  • Page 30: Eng] 2.6. [Dksf 48.5 Iu] How Can I Reboot The Device

    NetPing server room environmental monitoring solutions and IP power distribution units. [ENG] 2.6. [DKSF 48.5 IU] How Can I Reboot the Device? The NetPing device you can reboot using two ways: Press the " Reboot " button on the "HOME" page of the device`s web-interface.
  • Page 31: Eng] 3. [Dksf 48.5 Iu] Basic Configuration

    NetPing server room environmental monitoring solutions and IP power distribution units. [ENG] 3. [DKSF 48.5 IU] Basic Configuration Copyright © NetPing east Co., Ltd / E-mail: support@netpingdevice.com www.netpingdevice.com / Phone: +886-2-23121582...
  • Page 32: Eng] 3.1. [Dksf 48.5 Iu] How To Set Up A Hostname, A Location And The Contacts Of The Device

    SNMP – sysName. On default: empty line Device Location  – is a description of a place of installation of a Netping device. It is displayed on the home page and in the heading of a web interface, is available via SNMP – sysLocation.  On default : empty row Contact – is the administrator's contacts (usually, an e-mail).
  • Page 33: Eng] 3.2. [Dksf 48.5 Iu] Where Can I Change The Settings Of The Network Interface

    NetPing server room environmental monitoring solutions and IP power distribution units. [ENG] 3.2. [DKSF 48.5 IU] Where Can I Change the Settings of the Network Interface To change network interface parameters, such as an HTTP port, a server and an SNMP agent, there is a need to go to the page «...
  • Page 34: Eng] 3.3. [Dksf 48.5 Iu] Changing A Username And A Password

    NetPing server room environmental monitoring solutions and IP power distribution units. [ENG] 3.3. [DKSF 48.5 IU] Changing a Username and a Password To change a username and a password, there is a need to go to the web page «...
  • Page 35: Eng] 3.4. [Dksf 48.5 Iu] How To Set The Community For Snmp

    NetPing server room environmental monitoring solutions and IP power distribution units. [ENG] 3.4. [DKSF 48.5 IU] How to Set the Community for SNMP? To configure Community, there is a need to go to the web page « Setup » of a device web interface: In the section «...
  • Page 36: Eng] 3.5. [Dksf 48.5 Iu] How To Restrict The Access To The Device

    NetPing server room environmental monitoring solutions and IP power distribution units. [ENG] 3.5. [DKSF 48.5 IU] How to Restrict the Access to the Device? To restrict an access to a device via HTTP and SNMP protocols, there is a need to go to the page «...
  • Page 37: Eng] 3.6. [Dksf 48.5 Iu] How To Turn Off All Notifications Quickly

    NetPing server room environmental monitoring solutions and IP power distribution units. [ENG] 3.6. [DKSF 48.5 IU] How to Turn Off All Notifications Quickly? It is possible to disable all notification types at the page « Setup » of a device web interface. To do this, there is a need to check a checkbox «...
  • Page 38: Eng] 3.7. [Dksf 48.5 Iu] There Is A Need To Send Snmp Trap Notifications. How Can I Configure This

    NetPing server room environmental monitoring solutions and IP power distribution units. [ENG] 3.7. [DKSF 48.5 IU] There is a need to send SNMP Trap Notifications. How Can I Configure This? IP-addresses for sending SNMP TRAP notifications are configured on the page «...
  • Page 39: Eng] 3.8. [Dksf 48.5 Iu] How To Set Up The Clock

    NetPing server room environmental monitoring solutions and IP power distribution units. [ENG] 3.8. [DKSF 48.5 IU] How to Set up The Clock? SETTING THE CLOCK MANUALLY To set the clock manually, there is a need to go to the page «...
  • Page 40 NetPing server room environmental monitoring solutions and IP power distribution units. To use the NTP servers from the Internet, a device is going to have a gateway correctly configured, and a device should have the Internet connection via an NTP protocol.
  • Page 41: Eng] 3.9. [Dksf 48.5 Iu] I Want To Configure Syslog. How Can I Do It

    NetPing server room environmental monitoring solutions and IP power distribution units. [ENG] 3.9. [DKSF 48.5 IU] I Want to Configure SYSLOG. How Can I do It? Transfer of notifications to the SYSLOG server is configured at the page « Setup »...
  • Page 42: Eng] 3.10. [Dksf 48.5 Iu] How To Receive Notifications And Reports Via Email

    NetPing server room environmental monitoring solutions and IP power distribution units. [ENG] 3.10. [DKSF 48.5 IU] How to Receive Notifications and Reports via Email? To configure the module for sending e-mail notifications and reports about a status, there is a need to go to the page «...
  • Page 43: Eng] 3.11. [Dksf 48.5 Iu] How To Update The Firmware Of The Device

    NetPing server room environmental monitoring solutions and IP power distribution units. [ENG] 3.11. [DKSF 48.5 IU] How to Update the Firmware of the Device? There is a need to do the following to update an embedded firmware version: Download an up-to-date firmware from the official website of the company (section «...
  • Page 44: Eng] 3.12. [Dksf 48.5 Iu] What Messages Are There In The System Log

    NetPing server room environmental monitoring solutions and IP power distribution units. [ENG] 3.12. [DKSF 48.5 IU] What Messages are There in the System Log? The page «LOG»  of a web interface represents a device operation. In the log file events of a device are recorded in a chronological order. All notifications of the log file are duplicated via SYSLOG protocol, if an IP address of the SYSLOG server is specified in the settings of a device.
  • Page 45 NetPing server room environmental monitoring solutions and IP power distribution units. Thermo: channel N "XXXX" , below normal ..BBC  – is recorded into the log file when readings of a temperature sensor are below the limits of a range specified by a user when notifications from a temperature sensor are enabled in the log file .
  • Page 46 NetPing server room environmental monitoring solutions and IP power distribution units. channel, specified by a user at the page of a web interface. YYYY – is a name of a relay management mode. The next modes are possible: «switched off manually», «switched on manually», «watchdog management», «schedule management», «schedule and watchdog management», «logic management».
  • Page 47 NetPing server room environmental monitoring solutions and IP power distribution units. GSM modem is ready for operation – is recorded into the log file after a GSM modem has been initialized in the system. When a parameter «Register exchange with a GSM modem to the log is enabled at the page »...
  • Page 48: Eng] 4. [Dksf 48.5 Iu] Working With Temperature Sensors

    NetPing server room environmental monitoring solutions and IP power distribution units. [ENG] 4. [DKSF 48.5 IU] Working with Temperature Sensors Copyright © NetPing east Co., Ltd / E-mail: support@netpingdevice.com www.netpingdevice.com / Phone: +886-2-23121582...
  • Page 49: Eng] 4.1. [Dksf 48.5 Iu] Which Temperature Sensors Are Supported By The Device

    NetPing server room environmental monitoring solutions and IP power distribution units. [ENG] 4.1. [DKSF 48.5 IU] Which Temperature Sensors are Supported by the Device The device supports connecting temperature sensors of the 1-Wire type.   The device does not support the temperature sensors of the TS and WT types.
  • Page 50: Eng] 4.2. [Dksf 48.5 Iu] How To Detect A Unique Id Number Of A 1-Wire Temperature Sensor

    NetPing server room environmental monitoring solutions and IP power distribution units. [ENG] 4.2. [DKSF 48.5 IU] How to Detect a Unique ID number of a 1-Wire Temperature Sensor? To read a unique Id of a 1-Wire sensor, there is a need to go to the page «...
  • Page 51: Eng] 4.3. [Dksf 48.5 Iu] Where To See The Current Temperature

    NetPing server room environmental monitoring solutions and IP power distribution units. [ENG] 4.3. [DKSF 48.5 IU] Where to See the Current Temperature? To see a current temperature of temperature sensors, there is a need to go to the page «...
  • Page 52: Eng] 4.4. [Dksf 48.5 Iu] Is It Possible To Set A Description For Current Sensors

    NetPing server room environmental monitoring solutions and IP power distribution units. [ENG] 4.4. [DKSF 48.5 IU] Is it Possible to Set a Description for Current Sensors? To set a description for temperature sensors, there is a need to go to the page «...
  • Page 53: Eng] 4.5 [Dksf 48.5 Iu] Setting Up And Top And The Bottom Margins Of The Norm For Temperature Sensors

    NetPing server room environmental monitoring solutions and IP power distribution units. [ENG] 4.5 [DKSF 48.5 IU] Setting Up and Top and the Bottom Margins of the Norm for Temperature Sensors To configure a top and bottom margin of a safe range for a temperature sensor, there is a need to go to the page «...
  • Page 54: Eng] 4.6. [Dksf 48.5 Iu] I Want To Configure Sending The Notifications When A Status Of A Temperature Sensor Is Changed. How To Do This

    NetPing server room environmental monitoring solutions and IP power distribution units. [ENG] 4.6. [DKSF 48.5 IU] I Want to Configure Sending the Notifications When a Status of a Temperature Sensor is changed. How to Do This? Sending notifications when a status of a temperature sensor is changed is configured at the page «...
  • Page 55: Eng] 5. [Dksf 48.5 Iu] Working With A Humidity Sensor

    NetPing server room environmental monitoring solutions and IP power distribution units. [ENG] 5. [DKSF 48.5 IU] Working with a Humidity Sensor. Copyright © NetPing east Co., Ltd / E-mail: support@netpingdevice.com www.netpingdevice.com / Phone: +886-2-23121582...
  • Page 56: Eng] 5.1. [Dksf 48.5 Iu] Which Humidity Sensors Are Supported By The Device

    NetPing server room environmental monitoring solutions and IP power distribution units. [ENG] 5.1. [DKSF 48.5 IU] Which Humidity Sensors are Supported By the Device? The device does not support humidity sensors of the WS type Устройство поддерживает подключение датчиков влажности типа 1-Wire. The device supports the connecting the humidity sensors of the 1-Wire type. ...
  • Page 57: Eng] 5.2. [Dksf 48.5 Iu] How To Determine A Unique Id Number Of A 1 Wire Humidity Sensor

    NetPing server room environmental monitoring solutions and IP power distribution units. [ENG] 5.2. [DKSF 48.5 IU] How to Determine a Unique ID number of a 1 Wire Humidity Sensor? To read a unique Id of a 1-Wire sensor, there is a need to go to the page «...
  • Page 58: Eng] 5.3. [Dksf 48.5 Iu] Initial Configuration Of A Humidity Sensor

    NetPing server room environmental monitoring solutions and IP power distribution units. [ENG] 5.3. [DKSF 48.5 IU] Initial Configuration of a Humidity Sensor At the page «HUMIDITY» of the device web interface, readings of humidity sensors connected to the device are displayed. Up to four humidity sensors of the 1-Wire model line can be connected to the device.
  • Page 59: Interface

    NetPing server room environmental monitoring solutions and IP power distribution units. [ENG] 5.4. [DKSF 48.5 IU] Viewing Readings and Configuring Parameters of the Humidity Sensor in a Web Interface To browse readings and a configuration of humidity sensor parameters, there is a need to go to the page «...
  • Page 60: Eng] 5.5. [Dksf 48.5 Iu] I Want To Configure Sending Notifications When The Status Of The Humidity Sensor Is Changed. How Can I Do It

    NetPing server room environmental monitoring solutions and IP power distribution units. [ENG] 5.5. [DKSF 48.5 IU] I Want to Configure Sending Notifications When the Status of the Humidity Sensor is Changed. How Can I Do It? Sending notifications when the status of a humidity sensor is changed is configured on the page «HUMIDITY» of the device`s web interface: When clicking the button «Setup», a menu of settings for sending notifications of the next types appears: Log, Syslog, Email, SMS and SNMP...
  • Page 61 NetPing server room environmental monitoring solutions and IP power distribution units. humidity range. In default : checkbox is not checked Temperature is above Safe Range — is a checkbox, when checked, a device will send notifications if the temperature exceeds the top margin of the safe temperature range.
  • Page 62: Eng] 6. [Dksf 48.5 Iu] Working With 1W Smoke Sensors

    NetPing server room environmental monitoring solutions and IP power distribution units. [ENG] 6. [DKSF 48.5 IU] Working with 1W Smoke Sensors Copyright © NetPing east Co., Ltd / E-mail: support@netpingdevice.com www.netpingdevice.com / Phone: +886-2-23121582...
  • Page 63: Eng] 6.1. [Dksf 48.5 Iu] What Smoke Sensors Are Supported By The Device

    NetPing server room environmental monitoring solutions and IP power distribution units. [ENG] 6.1. [DKSF 48.5 IU] What Smoke Sensors are Supported By the Device? The device does not support the operation with a smoke detector (mod. M206-5E) The device supports the connectionof the smoke sensors of 1 Wire type.
  • Page 64: Eng] 6.2. [Dksf 48.5 Iu] How To Determine The Unique Number Of A 1W Smoke Sensor

    NetPing server room environmental monitoring solutions and IP power distribution units. [ENG] 6.2. [DKSF 48.5 IU] How to Determine the Unique Number of a 1W Smoke Sensor? To read a unique Id of a 1-Wire sensor, there is a need to go to the page «...
  • Page 65: Eng] 6.3. [Dksf 48.5 Iu] Initial Configuration Of Smoke Sensors

    NetPing server room environmental monitoring solutions and IP power distribution units. [ENG] 6.3. [DKSF 48.5 IU] Initial Configuration of Smoke Sensors The “ SMOKE ” page of the device’s web interface displays the status of smoke detectors connected to the device. Four smoke detectors of the 1-Wire model range can be connected to the device.
  • Page 66: Eng] 6.4. [Dksf 48.5 Iu] Is It Possible To Set The Description For Smoke Sensors

    NetPing server room environmental monitoring solutions and IP power distribution units. [ENG] 6.4. [DKSF 48.5 IU] Is It Possible to Set the Description for Smoke Sensors? To set a description for smoke sensors, there is a need to go to the page «...
  • Page 67: Eng] 6.5. [Dksf 48.5 Iu] How Can I See The Current Status Of A Smoke Sensor

    NetPing server room environmental monitoring solutions and IP power distribution units. [ENG] 6.5. [DKSF 48.5 IU] How Can I See The Current Status of a Smoke Sensor? To see a current status of smoke sensors, there is a need to go to the page «...
  • Page 68: Eng] 6.6. [Dksf 48.5 Iu] How To Turn On The Power And Reset The Smoke Sensor

    NetPing server room environmental monitoring solutions and IP power distribution units. [ENG] 6.6. [DKSF 48.5 IU] How to Turn On the Power and Reset the Smoke Sensor? Power supply or reset of smoke sensors is managed at the page «...
  • Page 69: Eng] 6.7. [Dksf 48.5 Iu] I Want To Configure Sending The Notifications When A Status Of A Smoke Sensor Is Changed. How To Do This

    NetPing server room environmental monitoring solutions and IP power distribution units. [ENG] 6.7. [DKSF 48.5 IU] I Want To Configure Sending the Notifications When a Status of a Smoke Sensor is changed. How To Do This? Sending notifications when a status of a smoke sensor is changed is configured at the page «...
  • Page 70: Eng] 7. [Dksf 48.5 Iu] Working With The Channels Of The Discrete Input-Output

    NetPing server room environmental monitoring solutions and IP power distribution units. [ENG] 7. [DKSF 48.5 IU] Working with the Channels of the Discrete Input-Output Copyright © NetPing east Co., Ltd / E-mail: support@netpingdevice.com www.netpingdevice.com / Phone: +886-2-23121582...
  • Page 71: Eng] 7.1. [Dksf 48.5 Iu] Is It Possible To Set A Description For The Input-Output Line

    NetPing server room environmental monitoring solutions and IP power distribution units. [ENG] 7.1. [DKSF 48.5 IU] Is It Possible to Set a Description for the Input-Output Line? To set a description for an input-output line, there is a need to go to the page «...
  • Page 72: Eng] 7.2. [Dksf 48.5 Iu] Configuring An Operation Mode For An Input-Output Line

    NetPing server room environmental monitoring solutions and IP power distribution units. [ENG] 7.2. [DKSF 48.5 IU] Configuring an Operation Mode for an Input-Output Line To configure an operation mode of an IO-line, there is a need to go to the page «...
  • Page 73: Eng] 7.3. [Dksf 48.5 Iu] How To Determine A Current Logic Level Of An Input-Output Line

    NetPing server room environmental monitoring solutions and IP power distribution units. [ENG] 7.3. [DKSF 48.5 IU] How to Determine a Current Logic Level of an Input-Output Line? To define a current logic level of an IO line, there is a need to go to the page «...
  • Page 74: Eng] 7.4. [Dksf 48.5 Iu] How To Control An Input-Output Line In An "Output

    NetPing server room environmental monitoring solutions and IP power distribution units. [ENG] 7.4. [DKSF 48.5 IU] How to Control an Input-Output Line in an "Output" To control an IO-line, there is a need to go to the page « DISCRETE IO »...
  • Page 75: Eng] 7.5. [Dksf 48.5 Iu] I Want To Configure Sending Notifications When A Logic Level Of An Io Line Is Changed. How To Do This

    NetPing server room environmental monitoring solutions and IP power distribution units. [ENG] 7.5. [DKSF 48.5 IU] I Want to Configure Sending Notifications When a Logic Level of an IO Line is changed. How to Do This? Sending notifications are configured when the logical level of the IO line is changed on the “...
  • Page 76 NetPing server room environmental monitoring solutions and IP power distribution units. Colour - the choice of the color of the virtual logical level indicator, which is displayed on the “DISCRETE IO” page (the color of the physical LED indicators on the front panel cannot be adjusted), possible options are “white”, “gray”, “orange”, “red”, “ green".
  • Page 77: Eng] 7.6. [Dksf 48.5 Iu] What Do I Need A Filter Out Short Noise Pulses In The Parameters Of Discrete Io Line For

    NetPing server room environmental monitoring solutions and IP power distribution units. [ENG] 7.6. [DKSF 48.5 IU] What Do I Need a Filter out Short Noise Pulses in the Parameters of Discrete IO Line for? Filter out short noise pulses (20-10 000 ms) - is a field for setting a period of time, during which an IO line configured as an «...
  • Page 78: Eng] 8. [Dksf 48.5 Iu] Working With A Built-In Relay

    NetPing server room environmental monitoring solutions and IP power distribution units. [ENG] 8. [DKSF 48.5 IU] Working with a Built-In Relay Copyright © NetPing east Co., Ltd / E-mail: support@netpingdevice.com www.netpingdevice.com / Phone: +886-2-23121582...
  • Page 79: Eng] 8.1 [Dksf 48.5 Iu] The Control Switch Of The Relay

    NetPing server room environmental monitoring solutions and IP power distribution units. [ENG] 8.1 [DKSF 48.5 IU] The Control Switch of the Relay The control switch of the built-in relay is carrie out on the " AC OUTLETS " page of the device`s web-interface: This page allows you to control the eight output channels (relays) of the device power supply.
  • Page 80: Eng] 8.2 [Dksf 48.5 Iu] I Want To Configure The Sending Of Notifications For Events About The Operation Of The Relay. How To Do It

    NetPing server room environmental monitoring solutions and IP power distribution units. [ENG] 8.2 [DKSF 48.5 IU] I Want to Configure the Sending of Notifications for Events About the Operation of the Relay. How to Do It? In order to configure the notifications about the operation you need to open the "...
  • Page 81 NetPing server room environmental monitoring solutions and IP power distribution units. .1.3.6.1.4.1.25728.5500.6.S.99, where S — an event, possible values: 100 (Off), 101 (On), 102 (the command fo the relay state change has been received), 103 (the reset of the relay has been started);...
  • Page 82: Eng] 8.3. [Dksf 48.5 Iu] What Is "Watchdog" And Can It Be Configured

    NetPing server room environmental monitoring solutions and IP power distribution units. [ENG] 8.3. [DKSF 48.5 IU] What is "Watchdog" and Can it Be Configured? «Watchdog» — is a specific operation mode of a relay channel. In this mode, specified addresses are pinged by ping (ICMP Echo) with a set frequency.
  • Page 83 NetPing server room environmental monitoring solutions and IP power distribution units. where: Enable Control of Relay — the activation of the relay control.If the checkbox is not installed, the relay will not be controlled from the "Watchdog" odule. In Default: the checkbox is not installed.
  • Page 84 NetPing server room environmental monitoring solutions and IP power distribution units. Ping Polling Pause After Reset  (1 3600) –  — a field for setting the time for which polling is suspended after turning on the power channel socket. A pause is necessary for the device to reboot, initialize and restore the functioning of its network interfaces. Otherwise, an endless repetition of the operation of the "Watchdog"...
  • Page 85: Eng] 8.4. [Dksf 48.5 Iu] What Is A "Schedule" And How To Configure It

    NetPing server room environmental monitoring solutions and IP power distribution units. [ENG] 8.4. [DKSF 48.5 IU] What is a "Schedule" and How to Configure It? A « Schedule » module allows configuring a schedule according to which a relay is going to switch on and off.
  • Page 86 NetPing server room environmental monitoring solutions and IP power distribution units. the format " hh:mm " in the range of 00:00 - 23:59 . The time should increase from left to right: in the interval, the switch-on time should come earlier than the switch-off time, the switch-on time in interval 2 should come later than the switch-off time in interval 1.
  • Page 87: Eng] 9. [Dksf 48.5 Iu] Working With Ac Power Inputs

    NetPing server room environmental monitoring solutions and IP power distribution units. [ENG] 9. [DKSF 48.5 IU] Working with AC Power Inputs Copyright © NetPing east Co., Ltd / E-mail: support@netpingdevice.com www.netpingdevice.com / Phone: +886-2-23121582...
  • Page 88: Eng] 9.1. [Dksf 48.5 Iu] Configuration Of The Ac Inputs In The Device`s Web Interface

    NetPing server room environmental monitoring solutions and IP power distribution units. [ENG] 9.1. [DKSF 48.5 IU] Configuration of the AC Inputs in the Device`s Web Interface The Configuration of the AC inputs if carried out on the " AC OUTLETS "...
  • Page 89: Eng] 9.2. [Dksf 48.5 Iu] How To Configure Notifications From The Power Inputs Of The Device

    NetPing server room environmental monitoring solutions and IP power distribution units. [ENG] 9.2. [DKSF 48.5 IU] How to Configure Notifications From the Power Inputs of the Device? The notifications configuration of the power inputs of the device is carried out on the “...
  • Page 90: Eng] 10. [Dksf 48.5 Iu] Work With The "Logic" Module

    NetPing server room environmental monitoring solutions and IP power distribution units. [ENG] 10. [DKSF 48.5 IU] Work With the "LOGIC" Module Copyright © NetPing east Co., Ltd / E-mail: support@netpingdevice.com www.netpingdevice.com / Phone: +886-2-23121582...
  • Page 91: Eng] 10.1. [Dksf 48.5 Iu] What Is "Logic

    » of a device web interface describes an operating algorithm of a module and its configuration capabilities. It is prohibited to use a NetPing device to manage electrical circuits when a violation of the control may cause a significant damage.
  • Page 92: Eng] 10.2. [Dksf 48.5 Iu] How Can I Use The "Logic" Module

    NetPing server room environmental monitoring solutions and IP power distribution units. [ENG] 10.2. [DKSF 48.5 IU] How Can I Use the "LOGIC" Module? IMPORTANT . In the updated module " LOGIC " (beginning with  the DKSF 48.5 firmware version), all the rules are identical to the rules of the "...
  • Page 93 NetPing server room environmental monitoring solutions and IP power distribution units. For more details look has finished  The rule is triggered in 10 seconds after the reset. here   — [ENG] 10.6. [DKSF 48.5 IU] Reset Signal and Initial Output States IO-line 1..8...
  • Page 94 NetPing server room environmental monitoring solutions and IP power distribution units. Timer/Counter 1...4 The control of a built-in timer/counter  set from 0 (the timer Start the timer from 0. The countdown is function) carried out in seconds with a resolution of 0 ...
  • Page 95: Eng] 10.4. [Dksf 48.5 Iu] How Can I Configure The Pinger In The Logic Module

    NetPing server room environmental monitoring solutions and IP power distribution units. [ENG] 10.4. [DKSF 48.5 IU] How Can I Configure The Pinger in the Logic Module? In order to configure the pinger you have to open the " LOGIC " page of the device`s web interface: ...
  • Page 96: Eng] 10.5. [Dksf 48.5 Iu] What Is Snmp Setter

    ” module rule and you need it to set the SNMP OID variable value on the remote device using SNMP v1 protocol. In particular, you can control IO lines, relays, and other parameters of a remote NetPing device over a network.
  • Page 97: Eng] 10.6. [Dksf 48.5 Iu] Reset Signal And Initial Output States

    NetPing server room environmental monitoring solutions and IP power distribution units. [ENG] 10.6. [DKSF 48.5 IU] Reset Signal and Initial Output States   At the start of the logic, it is possible to set the outputs and the equipment they control in a known and predetermined initial state. To do this, use the rules with the entry "...
  • Page 98: Eng] 10.7. [Dksf 48.5 Iu] Ir Commands

    NetPing server room environmental monitoring solutions and IP power distribution units. [ENG] 10.7. [DKSF 48.5 IU] IR Commands The rule of the " LOGIC " module can be controlled by means the IR commands via the external  IRC-TR v2  module. First of all, you have to write the necessary commands from the remote control (s) to the cells 1 ...
  • Page 99: Eng] 10.8. [Dksf 48.5 Iu] The Examples Of The Configuration Of The "Logic" Module

    CONTROLLING TOO FREQUENT DOOR OPENING IN A SERVER ROOM ON THE BASIS OF A NEW MODULE "LOGIC" OF A NETPING DEVICE SEQUENTIAL SERVERS STARTUP WITH PAUSES ON THE BASIS OF THE NEW MODULE "LOGIC" OF A NETPING POWER DISTRIBUTION UNIT INTERMITTENT OPERATION OF THE VENTILATION SYSTEM ON THE BASIS OF A NEW MODULE "LOGIC"...
  • Page 100: Eng] 11. [Dksf 48.5 Iu] Work With The Operating Ir Module

    NetPing server room environmental monitoring solutions and IP power distribution units. [ENG] 11. [DKSF 48.5 IU] Work With the Operating IR Module Copyright © NetPing east Co., Ltd / E-mail: support@netpingdevice.com www.netpingdevice.com / Phone: +886-2-23121582...
  • Page 101: Eng] 11.1. [Dksf 48.5 Iu] How Can I Record Ir Commands Correctly

    NetPing server room environmental monitoring solutions and IP power distribution units. [ENG] 11.1. [DKSF 48.5 IU] How Can I Record IR Commands Correctly? An IR Control module works with an IR transceiver IRC-TR v2. The transceiver can record and reproduce IR signals from remote controls of home appliances. ...
  • Page 102: Eng] 11.2. [Dksf 48.5 Iu] Playback Of Ir Commands Via The Web Interface

    NetPing server room environmental monitoring solutions and IP power distribution units. [ENG] 11.2. [DKSF 48.5 IU] Playback of IR Commands Via the Web Interface An IR control module works with an IR transceiver IRC-TR v2. A transceiver can record and reproduce IR signals from remotes of home appliances. ...
  • Page 103: Eng] 11.3. [Dksf 48.5 Iu] Can I Play Back The Ir Commands Via Snmp

    You can download the MIB file on the device description pages in the websire or our company http://ww w.netpingdevice.com/products/netping-8-pwr-220-v4-sms. The recording of the commands is only possible with the help of the device`s web interface. ...
  • Page 104: Eng] 11.4. [Dksf 48.5 Iu] How Can I Determine The Version Of A Built-In Firmware Of Ir Module

    NetPing server room environmental monitoring solutions and IP power distribution units. [ENG] 11.4. [DKSF 48.5 IU] How Can I Determine the Version of a Built-In Firmware of IR Module? To determine a firmware version of an IR module, go to the web page «...
  • Page 105: Eng] 11.5. [Dksf 48.5 Iu] Recommendations

    If a transceiver is stuck in a protocol as a result of a failure, noise, an operator's error or managing software failure, and reacts improperly to incoming commands, a reset can be performed by a short-term (5 s.) switching off a transceiver from a NetPing device.
  • Page 106: Eng] 12. [Dksf 48.5 Iu] Work With Sms Messages And Built-In Gsm Modem

    NetPing server room environmental monitoring solutions and IP power distribution units. [ENG] 12. [DKSF 48.5 IU] Work with SMS Messages and Built-In GSM Modem Copyright © NetPing east Co., Ltd / E-mail: support@netpingdevice.com www.netpingdevice.com / Phone: +886-2-23121582...
  • Page 107: Eng] 12.1. [Dksf 48.5 Iu] How To Find Out A Ussd Balance On A Sim-Card

    NetPing server room environmental monitoring solutions and IP power distribution units. [ENG] 12.1. [DKSF 48.5 IU] How to Find Out a USSD Balance on a SIM-card In order to find out the balance on the SIM-card installed in the slot of the built-in GSM modem, open the “...
  • Page 108: Eng] 12.2. [Dksf 48.5 Iu] I Need To Configure The Number To Send Sms Notifications Sms-Уведомлений. How Can I Do This

    NetPing server room environmental monitoring solutions and IP power distribution units. [ENG] 12.2. [DKSF 48.5 IU] I Need to Configure the Number to Send SMS Notifications SMS-уведомлений. How Can I Do This? In order to set one or several phone numbers to sent SMS Notifications, you need to open the page "...
  • Page 109: Eng] 12.3. [Dksf 48.5 Iu] Gsm Modem Troubleshooting

    SMS NOTIFICATION DESTINATIONS AND SMS COMMANDS SOURCES"  on the page " " of the device`s web interface should get the SMS message with the text "NetPing SMS Test". Copyright © NetPing east Co., Ltd / E-mail: support@netpingdevice.com www.netpingdevice.com / Phone: +886-2-23121582...
  • Page 110: Eng] 12.4. [Dksf 48.5 Iu] The Gsm-Signal Strength Checking

    NetPing server room environmental monitoring solutions and IP power distribution units. [ENG] 12.4. [DKSF 48.5 IU] The GSM-Signal Strength Checking In order to check the registration and the  GSM-signal strength in a SIM card, inserted in the device, you need to open the page "...
  • Page 111: Eng] 12.5. [Dksf 48.5 Iu] The Receiving Of Sms-Notifications By Watchdog Events

    NetPing server room environmental monitoring solutions and IP power distribution units. [ENG] 12.5. [DKSF 48.5 IU] The Receiving of SMS-Notifications by Watchdog Events  For the configuration of SMS NOTIFICATIONS by watchdog events you need to open the page " " of the device`s web interface: ...
  • Page 112: Eng] 12.6. [Dksf 48.5 Iu] How Can I Configure The Forwarding Of Incoming Unrecognized Sms As A Command

    NetPing server room environmental monitoring solutions and IP power distribution units. [ENG] 12.6. [DKSF 48.5 IU] How can I Configure the Forwarding of Incoming Unrecognized SMS As a Command? The device firmware provides the possibility to configure SMS forwarding, which were unrecognized as commands: to the log;...
  • Page 113: Eng] 12.7. [Dksf 48.5 Iu] What Kinds Of Sms Notifications Can This Device Send

    SMS messages up to 30 Latic characters. The name is set on the page "SETUP" of the device`s web interface. If the name of the device is not set, the "NETPING" name is used instead of it. ...
  • Page 114 NetPing server room environmental monitoring solutions and IP power distribution units. n — number of the smoke sensor, 1...4; label  - a label of a temperature sensor which is set in the entry field “ Memo ” on the page “ SMOKE ”...
  • Page 115 NetPing server room environmental monitoring solutions and IP power distribution units. Message from the groups of outlets OUTLETS SWITCHED TO AC INPUT i "label" where: gg — a group of the input outlets, 1...4 or 5...8; i — power input number, 1 или 2;...
  • Page 116: Eng] 12.8. [Dksf 48.5 Iu] How Can I Control The Device Using Sms Commands

    NetPing server room environmental monitoring solutions and IP power distribution units. [ENG] 12.8. [DKSF 48.5 IU] How Can I Control The Device using SMS Commands? The device has an ability to be controlled remotely using SMS commands. THE SYNTAX OF SMS COMMANDS The common format of an SMS command text: NETPING fff community_w kkkkkk...
  • Page 117 NetPing server room environmental monitoring solutions and IP power distribution units. Return to the primary input for outlets group x, where x is the number of outlet group: 1 (outlets 1 ... 4) or 2 (outlets 5 ... 8) Set the line m to log. 1, where m is the number of the IO line.
  • Page 118 NetPing server room environmental monitoring solutions and IP power distribution units. NP WRONG PASSWD where: kkkkk — a request identifier (arbitrary number from 3 to 9 digits). It is repeated in the response to establish the correspondence between the request and the response. An optional command element. If the identifier is not in the command, you can not see it in the response (the second command).
  • Page 119 NetPing server room environmental monitoring solutions and IP power distribution units. NP REPLY N=status ( address where: status — the pinger status, 0 — silent, 1 — responding address — The IP or domain name of the polled host Response to the request Tb? NP REPLY T ? SENSOR FAILED  —...
  • Page 120: Eng] 12.9. [Dksf 48.5 Iu] Setting The Time For Sending A Summary Report About The Status Of Sensors And Io Lines In The Form Of Sms Messages

    NetPing server room environmental monitoring solutions and IP power distribution units. [ENG] 12.9. [DKSF 48.5 IU] Setting the Time for Sending a Summary Report About the Status of Sensors and IO Lines in the Form of SMS Messages To adjust time of sending a daily report about a status of sensors and IO lines as SMS notifications, there is a need to go to the page «...
  • Page 121: Eng] 12.10. [Dksf 48.5 Iu] How To Know Imei Of A Built-In Gsm Modem

    NetPing server room environmental monitoring solutions and IP power distribution units. [ENG] 12.10. [DKSF 48.5 IU] How to Know IMEI of a Built-In GSM Modem? To get an IMEI (International Mobile Station Equipment Identity) of a built-in GSM modem, there is a need to go to a service page of a web-interface of a device via the address: http://192.168.0.100/at.html...
  • Page 122: Eng] 12.11. [Dksf 48.5 Iu] How To Send Arbitrary Sms

    In NetPing devices, it is community=SWITCH on default;  IP  is an IP address of a NetPing device, through which a random SMS message will be sent;  – OID  is an SNMP identifier of a variable –...
  • Page 123 NetPing server room environmental monitoring solutions and IP power distribution units. Based on the above description, a command for sending a random SMS using the utility snmpset.exe C:\Program Files (x86)\net-snmp\usr\bin>snmpset.exe -v 1 -c SWITCH 192.168.0.100 .1.3.6.1.4.1.25728.3800.1.9.0 s "[+79130000000] Hello! Test SMS!"...
  • Page 124 $resp.Close()  where: $url – is a variable, which sets an IP address of a NetPing device and a script for sending random SMS messages. $username – is a variable, which sets a username for authorization on a NetPing device. $password – is a variable, which sets a password for authorization on a NetPing device.
  • Page 125: Eng] 13. [Dksf 48.5 Iu] Device Support For Custom Notifications

    NetPing does not have a client`s HTTP/HTTPS, and to complete the request, it accesses the proprietary cloud service webhook.netping   .ru. It is transparent, does not remember and does not accumulate information passed through it. Available for any NetPing device and does not require any prior authorization and configuration.
  • Page 126 NetPing server room environmental monitoring solutions and IP power distribution units. HTTP GET-notification: Еmail- notification: The description of sensors and events: When you use the channel number “any channel”, it is recommended to use the substitution with the channel number so that the notification contains information about the sensor which caused this notification.
  • Page 127 The recipient cannot be set, messages are sent to the recipients specified on the "EMAIL" page. You can put the information from the NetPing MIB branch related to the sensor, IO line, or the relay that caused the event in the custom notification text.
  • Page 128 NetPing server room environmental monitoring solutions and IP power distribution units. .1.3 .6.1.4.1.25728.8800.1 .1. .n npThermoMemo The memo of the Temperature Sensor , where  n   a number of — sensor 1..8. .1.3.6.1.4.1.25728.8800.1.1. .n npThermoStatus The Status of the Sensor , where  n ...
  • Page 129: Eng] 14. [Dksf 48.5 Iu] Device Supporting Snmp Protocol

    NetPing server room environmental monitoring solutions and IP power distribution units. [ENG] 14. [DKSF 48.5 IU] Device Supporting SNMP Protocol Copyright © NetPing east Co., Ltd / E-mail: support@netpingdevice.com www.netpingdevice.com / Phone: +886-2-23121582...
  • Page 130: Eng] 14.1. [Dksf 48.5 Iu] Snmp Protocole Device Support

    NetPing server room environmental monitoring solutions and IP power distribution units. [ENG] 14.1. [DKSF 48.5 IU] SNMP Protocole Device Support  The  NetPing 8/PWR-220 v4/SMS device supports parameter setting and SNMP v1 operation. You can read more about SNMP at these links: https://en.wikipedia.org/wiki/Simple_Network_Management_Protocol...
  • Page 131: Eng] 14.2. [Dksf 48.5 Iu] Configuration Of Sending Snmp Trap Messages

    NetPing server room environmental monitoring solutions and IP power distribution units. [ENG] 14.2. [DKSF 48.5 IU] Configuration of Sending SNMP TRAP Messages To send  TRAP messages via SNMP v1 protocol using this device, it is necessary to configure the following parameters on the "...
  • Page 132: Eng] 14.3. [Dksf 48.5 Iu] Which Oid Are Supported By The Device

    NetPing server room environmental monitoring solutions and IP power distribution units. [ENG] 14.3. [DKSF 48.5 IU] Which OID are Supported By the Device? You can see the description of OID supported by the device in the table below: Name Type...
  • Page 133 NetPing server room environmental monitoring solutions and IP power distribution units. .1.3.6.1.4.1.25728.3800.1.9.0 npGsmSendSMS DisplayString READ/WRITE The sending an arbitrary SMS message Format: [phone_number,phone_number,...] Message where: phone_number — the recipient number in square brackets Message — message text (written with a space from the recipient number) Only latin letters are allowed in the SMS text.
  • Page 134 NetPing server room environmental monitoring solutions and IP power distribution units. .1.3.6.1.4.1.25728.5100.55.1.2.n npOutGrpBackupStatus.n Integer READ Input reservation status for outlets group, where n is the index of outlet group 1 or 2. Possible values: 0 - the outlet group is powered from the primary input 1 - the group of outlets is powered from the backup input .1.3.6.1.4.1.25728.5100.55.1.3.n...
  • Page 135 NetPing server room environmental monitoring solutions and IP power distribution units. .1.3.6.1.4.1.25728.8200.1.1.4.n npSmokeReset.n Integer READ/WRITE Write the number “1” to switch off the sensor for 10 seconds, where n is the number of the smoke sensor, the number from 1 to 4 inclusive .1.3.6.1.4.1.25728.8200.1.1.6.n...
  • Page 136 NetPing server room environmental monitoring solutions and IP power distribution units. .1.3.6.1.4.1.25728.8900.1.1.3.n npIoLevelOut.n Integer READ/WRITE The line status in the "output" mode, where n is the line number, a number from 1 to 4 inclusive. Write “1” or “0” to switch the line to the appropriate state.
  • Page 137: Eng] 14.4. [Dksf 48.5 Iu] The Support Of Snmp Trap

    NetPing server room environmental monitoring solutions and IP power distribution units. [ENG] 14.4. [DKSF 48.5 IU] The Support of SNMP trap A formal description of SNMP TRAP messages can be found in the DKSF 48.5.X MB MIB file attached to the firmware. It can be downloaded on the device description page in the "Documentation and Files"...
  • Page 138 NetPing server room environmental monitoring solutions and IP power distribution units. .1.3.6.1.4.1.25728.8800.2.3. Integer Sensor status:  0 — failed or not connected sensor 1 — temperature is below safe range 2 — temperature is in safe range 3 — temperature is above safe range .1.3.6.1.4.1.25728.8800.2.4.
  • Page 139 NetPing server room environmental monitoring solutions and IP power distribution units. Identification npRelHumTrap SNMP v2 snmpTrapOID .1.3.6.1.4.1.25728.8400.7.0.1 snmpTrapOID npRelHumTrapTemp (SNMP TRAP-messages when the status of temperature changes) The Description .1.3.6.1.4.1.25728.8400.7.100.n The fault of the sensor, where n - number of the sensor 1...4 .1.3.6.1.4.1.25728.8400.7.101.n...
  • Page 140 NetPing server room environmental monitoring solutions and IP power distribution units. SNMP TRAP FROM «WATCHDOG» Identification  npPwrWdogTrap SNMP v1 enterprise .1.3.6.1.4.1.25728.5800.6 SNMP v1 generic-trap enterpriseSpecific(6) SNMP v1 specific-trap SNMP v2 snmpTrapOID .1.3.6.1.4.1.25728.5800.6.0.1 snmpTrapOID npPwrWdogTrap (SNMP TRAP messages from «Watchdog») The description .1.3.6.1.4.1.25728.5800.6.100.n...
  • Page 141 NetPing server room environmental monitoring solutions and IP power distribution units. SNMP TRAP WHEN CHANGING THE STATUS OF A RELAY (OUTLET) Identification  npRelayTrap SNMP v2 SNMPTrapOID .1.3.6.1.4.1.25728.5500.6.0.1 snmpTrapOID  npRelayTrap (SNMP TRAP-messages from the relay) Описание .1.3.6.1.4.1.25728.5500.6.100.n  Relay is Switched Off, where n - number of the relay 1...8 .1.3.6.1.4.1.25728.5500.6.101.n...
  • Page 142 NetPing server room environmental monitoring solutions and IP power distribution units. SNMP TRAP ON STATUS OF POWER INPUTS Identification npAcInTraps SNMP v1 enterprise .1.3.6.1.4.1.25728.5100.46 SNMP v1 generic-trap enterpriseSpecific(6) SNMP v1 specific-trap SNMP v2 SNMPTrapOID .1.3.6.1.4.1.25728.5100.46.0.1 Variable values in the set  npAcInTraps...
  • Page 143 NetPing server room environmental monitoring solutions and IP power distribution units. .1.3.6.1.4.1.25728.5100.56.2.0 Integer Power source for a group of outlets. Possible values: 0 — primary input 1 — backup input .1.3.6.1.4.1.25728.5100.56.6.0 DisplayString The memo of an outlets group . Fixed for 1 - “1 ... 4”, for 2 - “5 ... 8”...
  • Page 144: Eng] 15. [Dksf 48.5 Iu] Device Support Http Api

    NetPing server room environmental monitoring solutions and IP power distribution units. [ENG] 15. [DKSF 48.5 IU] Device Support HTTP API Copyright © NetPing east Co., Ltd / E-mail: support@netpingdevice.com www.netpingdevice.com / Phone: +886-2-23121582...
  • Page 145: Eng] 15.1. [Dksf 48.5 Iu] Io Lines Control

    NetPing server room environmental monitoring solutions and IP power distribution units. [ENG] 15.1. [DKSF 48.5 IU] IO Lines Control The interface of URL-encoded commands in this device can be used for integration with web-applications without SNMP protocole.The operating of IO lined can be implemented via the interface of URL-encoded commands.
  • Page 146 NetPing server room environmental monitoring solutions and IP power distribution units. where: N – the line number, indicated after ?io. Switching to an alternative (inverse) state. http://192.168.0.100/io.cgi?ioN=f where: N – the line number, indicated after ?io. Short-term switching to the inverse state, i.e., the issuance of a pulse.
  • Page 147 NetPing server room environmental monitoring solutions and IP power distribution units. Copyright © NetPing east Co., Ltd / E-mail: support@netpingdevice.com www.netpingdevice.com / Phone: +886-2-23121582...
  • Page 148: Eng] 15.2. [Dksf 48.5 Iu] The Control Of The Relay

    NetPing server room environmental monitoring solutions and IP power distribution units. [ENG] 15.2. [DKSF 48.5 IU] The Control of The Relay The interface of URL-encoded command in the device can be used for the integration with web applications without  the SNMP protocole. The relay control is available via the interface of URL-encoded commands.
  • Page 149 NetPing server room environmental monitoring solutions and IP power distribution units. http://192.168.0.100/relay.cgi?r n=f,10 Duration in seconds is indicated after the decimal point. Applicable to all modes RETURN VALUES An error is returned if the request format is incorrect as a result of setting an incorrect / invalid value for the relay number or relay mode.
  • Page 150: Eng] 15.3. [Dksf 48.5 Iu] Control Of The Power Inputs Backup

    NetPing server room environmental monitoring solutions and IP power distribution units. [ENG] 15.3. [DKSF 48.5 IU] Control of the Power Inputs Backup The interface of the URL-commands in the device can be used for integration with web-applications without SNMP protocole. The control of the power input backup is possible via the interface of the URL-encoded commands.
  • Page 151 NetPing server room environmental monitoring solutions and IP power distribution units. Error (wrong request format or wrong relay number): ats_in_result('error') Successful execution of the command ats_in_result('ok', 2) ats_in_result('ok', 'on') where: The first and only argument is 'error' if the command is not recognized or an invalid group number is specified The first argument is 'ok', if the second is followed by ...
  • Page 152 NetPing server room environmental monitoring solutions and IP power distribution units. ats_result('ok') SWITCHING ON/OFF THE AUTO RETURN Switching on ('on') or off ('off') automatic return to the main input when voltage is restored on it for groups of outlets /ats.cgi?gN&autorevert=on /ats.cgi?gN&autorevert=off ...
  • Page 153 NetPing server room environmental monitoring solutions and IP power distribution units. <URL‐path>?<parameters>   is a URL-encoded command – Copyright © NetPing east Co., Ltd / E-mail: support@netpingdevice.com www.netpingdevice.com / Phone: +886-2-23121582...
  • Page 154: Eng] 15.4. [Dksf 48.5 Iu] The Control Of The 1-Wire Smoke Sensors

    NetPing server room environmental monitoring solutions and IP power distribution units. [ENG] 15.4. [DKSF 48.5 IU] The Control of the 1-wire Smoke Sensors The interface of URL-encoded commands in the device can be used to integrate with web applications without using the SNMP protocol. Through the interface of URL-encoded commands, control of 1-wire smoke detectors is available.
  • Page 155 NetPing server room environmental monitoring solutions and IP power distribution units. AUTHORIZATION To add a login and password to the structure of a URL-encoded command, it is possible to use the next scheme: http://<username>:<password>@<host>:<port>/<URL‐path>?<parameters> where: <username>:<password>  – are credentials for authorization in a device ...
  • Page 156: Eng] 15.5. [Dksf 48.5 Iu] The Control Of Temperature Sensors

    NetPing server room environmental monitoring solutions and IP power distribution units. [ENG] 15.5. [DKSF 48.5 IU] The Control of Temperature Sensors The interface of URL-encoded commands in the device can be used to integrate with web applications without using the SNMP protocol. Via the interface of URL-encoded commands, control of temperature sensors is available.
  • Page 157: Eng] 15.6. [Dksf 48.5 Iu] Control Of The Humidity Sensors

    NetPing server room environmental monitoring solutions and IP power distribution units. [ENG] 15.6. [DKSF 48.5 IU] Control of the Humidity Sensors The interface of URL-encoded commands in the device can be used to integrate with web applications without using the SNMP protocol. Via the interface of URL-encoded commands, humidity sensor control is available.
  • Page 158: Eng] 15.7. [Dksf 48.5 Iu] Control Of The Transceiver Of The Ir Commands

    NetPing server room environmental monitoring solutions and IP power distribution units. [ENG] 15.7. [DKSF 48.5 IU] Control of the Transceiver of the IR Commands An interface of URL-encoded commands in a device can be used to integrate with web applications without using an SNMP protocol. It is possible to control an IR command transceiver t hrough the interface of URL-encoded commands.
  • Page 159: Eng] 15.8 [Dksf 48.5 Iu] Control Of The Gsm Modem

    NetPing server room environmental monitoring solutions and IP power distribution units. [ENG] 15.8 [DKSF 48.5 IU] Control of The GSM Modem The interface of URL-encoded commands in the device can be used to integrate with web applications without using the SNMP protocol. Via the interface of URL-encoded commands, control of the built-in GSM modem is available.
  • Page 160 NetPing server room environmental monitoring solutions and IP power distribution units. ussdsend_result("request_gsm_operator"); Copyright © NetPing east Co., Ltd / E-mail: support@netpingdevice.com www.netpingdevice.com / Phone: +886-2-23121582...

Table of Contents