NetPing 8/PWR-220 v4/SMS User Manual page 139

Hide thumbs Also See for 8/PWR-220 v4/SMS:
Table of Contents

Advertisement

NetPing server room environmental monitoring solutions and IP power distribution units.
Identification npRelHumTrap
SNMP v2 snmpTrapOID
snmpTrapOID npRelHumTrapTemp (SNMP TRAP-messages when the status of temperature changes)
OID
.1.3.6.1.4.1.25728.8400.7.100.n
.1.3.6.1.4.1.25728.8400.7.101.n
.1.3.6.1.4.1.25728.8400.7.102.n
.1.3.6.1.4.1.25728.8400.7.103.n
.1.3.6.1.4.1.25728.8400.7.127.n
.1.3.6.1.4.1.25728.8400.7.m.99
.1.3.6.1.4.1.25728.8400.7.127.99
Variable values in the set npRelHumTrap (varbind list)
OID
.1.3.6.1.4.1.25728.8400.3.1.0
.1.3.6.1.4.1.25728.8400.3.2.0
.1.3.6.1.4.1.25728.8400.3.4.0
.1.3.6.1.4.1.25728.8400.3.6.0
.1.3.6.1.4.1.25728.8400.3.7.0
.1.3.6.1.4.1.25728.8400.3.8.0
The combination of event type and channel number can be enabled by the corresponding checkboxes in the notification settings dialog:
Copyright © NetPing east Co., Ltd / E-mail:
.1.3.6.1.4.1.25728.8400.7.0.1
The fault of the sensor, where n - number of the sensor 1...4
The readings of the temperature sensor below Safe Range, where n - number of the sensor 1...4
The readings of the temperature sensor in Safe Range, where n - number of the sensor 1...4
The readings of the temperature sensor above Safe Range, where n - number of the sensor 1...4
Common snmpTrapOID for all the events, where n — number of the sensor
Common snmpTrapOID for all the channels, where m —  the code of the event (100, 101, 102, 103)
Common snmpTrapOID  for all the events and channels
The type of the data
Integer
The index of the sensor that initiated the sending of the TRAP message.
Integer
The value of the relative humidity,  %, or temperature
Integer
The status of the relative humidity and temperature
Possible values:
DisplayString
The memo (textual description of the sensor, encoding win1251)
Integer
The upper limit of the range of safe values for relative humidity or temperature,% or C
Integer
The lower limit of the range of safe values for relative humidity or temperature,% or C
support@netpingdevice.com www.netpingdevice.com
The Description
The description
0 — sensor failed or not connected
1 — the reading are below the safe range
2 — the reading are in the safe range
3 — the reading are above the safe range
/
°C 
 