SWITCHING ON/OFF THE AUTO RETURN
Switching on ('on') or off ('off') automatic return to the main input when voltage is restored on it for groups of outlets
/ats.cgi?gN&autorevert=on
/ats.cgi?gN&autorevert=off
where:
N — the number of the outlet groups, 1 (1...4) or 2 (5...8)
RETURN VALUES
An error is issued if the command format is incorrect, the group number is incorrect, or the backup parameter is incorrect.
ats_result('error')
Successful execution of the command
ats_result('ok')
MANUAL RETURN ONTO THE MAIN (PRIMARY) INPUT
The return of the groups of outletss to the main input, if previously they were automatically transferred to the reserve and there is voltage on the
main input:
/ats.cgi?g1&revert
/ats.cgi?g1&revert
where:
N — the number of the outlets groups, 1 (1..4) or 2 (5..8)
RETURN VALUES
An error is issued if the command format is incorrect:
ats_result('error')
Successful execution of the command
ats_result('ok')
AUTHORIZATION
To add a login and password to the structure of a URL-encoded command, it is possible to use the next scheme:
http://<username>:<password>@<host>:<port>/<URL‐path>?<parameters>
where:
<username>:<password>
<host> is an IP address of a device;
–
<port> is a port of an HTTP server;
–
<URL‐path>?<parameters> is a URL-encoded command