[8PWR] Power Supply Channels Management

Channels Management
A NetPing 8/PWRv3/SMS device has eight independent power supply channels. Each channel is managed by a normally closed relay. A relay
and tracks have a big power capacity reserve, which provides a high resistance of a device to overloading.
Each channel can be turned on or turned off independently from others by a command from a web-interface, by an SNMP command or an
SMS-message. Likewise it is possible to automatically turn on or turn off a power supply channel according to a schedule or using a functionality
of a Watchdog or a Logic. There is a need to remember that when a channel is managed by a functionality of a Watchdog or a Logic, it cannot be
turned on or turned off manually (through a web-interface, SNMP, SMS).
 
Inputs Reservation
A device supports power supply inputs reservation. With this purpose, output power supply channels are divided into two groups, with four
channels in each one. Group 1 – channels 1 - 4, Group 2 – channels 5 - 8. For each group a main input is set (1 or 2). Both groups can use the
same input as a main one.
In cases of failure of a main input, a group of channels can be switched to a backup input - it is optional and is configured in a web-interface of a
device. After recovery of a main input a group of channels returns back to it either automatically or by an administrator's command. This behavior
is also programmed in a web-interface of a device. Switching of a group of output channels from one input to another can be done from a
web-interface, by an SNMP command, SMS-message.
All switches between the inputs occur with a two-second power supply turning off of a group of channels.
Device's software guarantees consequent turning off (and consequent turning on) of output power supply channels while switching from a main
input to a backup one to reduce a value of the switched current.
Connecting a Load to Output Channels
When connecting a load to output power supply channels there is a need to take into account capacity limits of a NetPing 8/PWRv3/SMS device.
A maximum capacity of each channel separately is 1500 Watts. A maximum total capacity of four channels in one group is 1725 Watts. I.e., if a
consumer with a maximum capacity of 1500 Watts is connected to a channel 1, then it is possible to connect a total load no more than 225 Watts
to channels 2,3,4.
Each input can provide 3500Watts, therefore both groups of power supply channels can be fed from one input (1725Watts + 1725Watts =
3500Watts).