[ENG] 12.7. [DKSF 48.5 IU] What Kinds of SMS Notifications Can This Device Send?

SYNTAX OF SMS NOTIFICATIONS
SMS Notifications look like:
np_name (q) information 
where:
np_name —
is the name of the device for the identification of SMS messages up to 30 Latic characters. The name is set on the page "SETUP" of
the device`s web interface. If the name of the device is not set, the "NETPING" name is used instead of it. 
q — is the sequence number of messages. The number is nonvolatile. It does not reset when the power is switched off.  It is needed for the
 
registration of the missed (lost) messages.
Information - is the informative part of SMS messages.
INFORMATIVE PART OF SMS MESSAGES
 A messages from the temperature sensor
TEMP.SENSOR 
j "label"
IS FAILED
TEMP.SENSOR 
j "label"
IN SAFE RANGE (
TEMP.SENSOR 
j "label"
BELOW
TEMP.SENSOR j "label" ABOVE SAFE RANGE (
where:
j — number of a temperature sensor, 1...8.
label — a label of a temperature sensor which is set in the entry field "
 
web-interface. The label in the message text is enclosed in quotation marks. If the label is not specified (empty), then it is not included in
the SMS.
t1,
 t2 
—  
the thresholds of normal temperature range, °C.
t — current temperature, 
Messages from Humidity Sensor
RH FAILED
j
— humidity sensor failure (the sensor stopped responding to the poll)
RH
j ht
(above the safe range 
RH
j ht
(below the safe range 
RH
j ht
(in the safe range 
ht1 ht2  — the reading of the humidity are in the safe range.
RHj
is OK,
h status t status
,
 где:
j — number of temperature sensor, 1...4.
ht — relative humidity or temperature
ht1,
 ht2 
— 
the thresholds of normal relative humidity range and temperature
h — relative humidity;
t — temperature;
status — the status of readings:"in the safe range", "below the safe range", "above the safe range"
Messages about the che change in status of a smoke sensor
SMOKE SENS.
n "label"
 — 
where:
Copyright © NetPing east Co., Ltd / E-mail:
 — temperature sensor failure (the sensor stopped responding to the poll);
t1 
TO  ), NOW  C
t2
SAFE RANGE (
t1 
TO  ), NOW  C
t2
t1 
TO  ), NOW  C  - 
t2
°C
 .
ht1 ht2  —  the readings of humidity and temperature are above the safe range
...
)
ht1 ht2  — the readings of humidity and temperature are below the safe range
...
)
...
)
 — the connection with the sensor is restored
status
support@netpingdevice.com www.netpingdevice.com
t  — the readings have returned to the safe range; 
t
 — the temperature goes below the safe range:
t
 the temperature goes above the safe range;
Memo
" on the page "
/
TEMPERATURE
" of the device`s