NetPing 8/PWR-220 v4/SMS User Manual page 61

Hide thumbs Also See for 8/PWR-220 v4/SMS:
Table of Contents

Advertisement

NetPing server room environmental monitoring solutions and IP power distribution units.
humidity range.
In default
Temperature is above Safe Range — is a checkbox, when checked, a device will send notifications if the temperature exceeds the top
margin of the safe temperature range.
Temperature is in Safe
temperature range. I
Temperature is below Safe
temperature range. I
Sensor
fault —
is a checkbox, when checked, a device will send notifications if a connection with a sensor is lost/restored. I
checkbox is not checked.
Include in Summary
and/or SNMP Trap. The time for sending reports is configured at the «
sending SNMP Trap is indicated in the "
Checkboxes Use common snmpTrapOID for All
«
events from all humidity sensors as one snmpTrapOID notification or divide events and numbers of humidity sensors among different
snmpTrapOID notifications, up to sending completely individual ones. This allows receiving individual SNMP Trap-notifications for processing
them in monitoring systems, for example, humidity sensor 3 getting damp or a humidity sensor 2 is at the safe range. If a humidity sensor fails,
two SNMP Trap notifications are sent: one about humidity, and another one about temperature.
The description of snmpTrapOID of humidity and temperature from a humidity sensor:
snmpTrapOID
 If the "Use common snmpTrapOID for all events" and "Use common snmpTrapOID for all Sensor Numbers" checkboxes are not set, the event
code and sensor number are included in snmpTrapOID and can be used in the monitoring system to determine in detail the reason and source
.1.3.6.1.4.1.25728.8400.
D S N
. .
If the "Use a common snmpTrapOID for all events" checkbox is set, the event code S is always 127, for any event
.1.3.6.1.4.1.25728.8400.
D 127 N
.
.
If the checkbox "Use a common snmpTrapOID for all sensor numbers" is set, the event code N is always 99, for any event
.1.3.6.1.4.1.25728.8400.
D S 99
. .
If the checkboxes "Use common snmpTrapOID for all events" and "Use common snmpTrapOID for all sensor numbers" are set, the event code
.1.3.6.1.4.1.25728.8400.
D 127 99
.
.
After setting up all necessary parameters, click the button «Apply
Copyright © NetPing east Co., Ltd / E-mail:
: checkbox is not checked
I default
n
: checkbox is not checked
Range —
is a checkbox, when checked, a  device will send notifications, if the temperature is back to the safe
n
default
: checkbox is not checked
Range—
is a checkbox when checked, a device will send notifications if the temperature fell below the safe
n
default
: checkbox is not checked
Report —
is a checkbox, when checked, reports about a status of a humidity sensor will be emailed, sent in SMS
SETUP
" page in the "
Events» and
snmpTrapOID from the humidity sensor.
where:
D — a membership code of a Trap message, possible values: 6 (SNMP Trap humidity), 7 (SNMP Trap
temperature);
S — a sensor status code (event), possible values: 100 (fault), 101 (below Safe Range), 102 (in Safe Range), 103
(above Safe Range);
N — a sensor channel number code, possible values from 1 to 4
With this setting, the sensor status code is set to "127" - a common snmpTrapOID is obtained for all events
With this setting, the sensor channel number code is set to "99" - a common snmpTrapOID is obtained for all
channels
S is always 127, and the event code N is always 99, for any event
With this setting, the sensor status code is set to "127", and the sensor channel number code is set to "99" - a
common snmpTrapOID is obtained for all events and channels
support@netpingdevice.com www.netpingdevice.com
.
.
.
.
SMS
» and «
E-MAIL
SNMP TRAP
" section.
«Use common snmpTrapOID for all Sensor
The description
of the trap.
changes».
/
» pages , the configuration of a periodic
In default: checkbox is not checked.
Numbers»
 
can be used to direct all
/ Phone: +886-2-23121582
n
default
: