[8PWR] Using IO Lines for External Devices Management (in an Output Mode)

Input-Output (IO) lines of a device can be used for an input work as well as in an output mode for managing external devices.
A device has four IO lines, corresponding to contacts I1 – I4 of a terminal block. Lines configuration for work as an input or an output is made
through a controlling web-interface of a device. All four IO lines can be customized independently.
Lines management can be done by SNMP commands, URL-encoded commands, via a web-interface or using SMS-commands (for devices with
built-in GSM modem).
Such device functions as a watchdog and scheduled load management are NOT AVAILABLE for IO in an output mode.
Examples of using:
Remote servers reboot – an imitation of pressing "reset";
Remote management of an alarm, a light, a fan;
Management of an electric lock, electric gates on a remote object;
Management of smart home elements - watering flowers, opening-closing louvers, water pump, heating boiler, heaters, etc.
Remote management of a power installation (diesel generator, gasoline).
Important! Correct electrical coordination of IO lines is required when connecting external executive devices.
Important! IO lines do not have galvanic isolation with a device! Remember about electrical safety when using relays that commutate
220 V circuits. All work must be done by specialists with a correspondent qualification who have a permit to work with such a voltage!
It is acceptable to use intermediate relays with a power supply voltage 12 V from an external source. A ready socket can be used for IO lines
connection
NetPing AC/DIN socket
devices:
BM8070D a power relay 16А/250V for DIN-rail
page on the site
);
MP701 a power module switch (4 independent channels, 2 kW 10A each)
device model on the relay web page on the site
For more detailed information, please contact a technical support 
Electric parameters of IO lines
In the «output» mode:
the voltage of logic «1»: +5 V, resistance: 3,3 kOhm;
the voltage of logic «0»: 0 V, resistance: 51 Ohm.
In the «input» mode:
the voltage of logic «1»: > 2,31 V;
the voltage of logic «0»: < 0,99 V.
Equivalent Сircuit
Copyright © NetPing east Co., Ltd / E-mail:
. In addition, we can advise ready assembly relays of other manufacturers, which can be connected to our