Error (wrong request format or wrong relay number):
ats_in_result('error')
Successful execution of the command
ats_in_result('ok', 2)
ats_in_result('ok', 'on')
where:
The first and only argument is 'error' if the command is not recognized or an invalid group number is specified
The first argument is 'ok', if the second is followed by  the value of the requested parameter
The second argument is the value of the requested parameter: 1 or 2 for the number of the main (primary) input, 'on' or 'off' for backup and
auto-return.
CHOICE OF THE MAIN (PRIMARY) INPUT
To force a switch, set an alternative input number:
http://192.168.0.100/ats.cgi?gN&main=n
where:
N — the number of the outlets goups , 1 (1...4) or 2 (5...8);
n — the input number (1 or 2).
RETURN VALUE
The error is issued if the command format is incorrect, the group number or input number is incorrect (more than 2):
ats_result('error')
Successful execution of the command
ats_result('ok')
SWITCHING ON/OFF OF THE AUTO BACKUP
Switching on ('on') or switching off ('off') the automatic transition to the backup input in case of power failure at the main input for groups of outlets:
/ats.cgi?gN&backup=on
/ats.cgi?gN&backup=off 
where:
N — the number of outlets groups, 1 (1...4) ot 2 (5...8)
RETURN VALUE
The error is generated if the command format is incorrect, the group number is incorrect, or the backup parameter is incorrect:
ats_result('error')
Successful execution of the command
ats_result('ok')