NetPing server room environmental monitoring solutions and IP power distribution units.
channel
Smoke (1W) 1..4 / any channel
 IO line 1..4 / any channel
Relay 1...8 / any channel
Watchdog 1...8 / any channel
Signal 1..4 / any channel
Monitoring 220V
GSM
The Description of notification methods:
The
method of
notification
SMS
Arbitrary SMS notifications. At the beginning of the text of a custom SMS notification, you can specify up to four recipients by
specifying their phone numbers in square brackets, separated by commas. Numbers are indicated in the format "Countrycode
OperatorcodeCustomernumber
"[+79130000001, +79130000002, +79130000003, +79130000004] Houston, we have a problem!"
If you do not specify the recipients, i.e. there are no square brackets at the beginning of the text,  the SMS will be sent to the
numbers specified in the settings on the "
HTTP GET
The called URL of a third-party service or cloud application. In order to send these notifications, the following scheme is used:Net
Ping--SNMP TRAP -->
accessed via a white address and access to it must be from the outside.
email
The sending of the email notification is carried out to the addresses specified on the "
possible to set the subject of the message in the "
itself. The recipient cannot be set, messages are sent to the recipients specified on the "EMAIL" page.
You can put the information from the NetPing MIB branch related to the sensor, IO line, or the relay that caused the event in the custom
notification text. Format: { }, where N is the SNMP OID component located in front of the sensor index.
N
 For example, the text of the SMS notification "{6} - {3} ({4}°C - {5}°C), {2}°C" for the temperature sensor includes the following information from
the NetPing MIB branch of the tree:
The
The Complete OID of variable
Substitution
value from NetPing MIB
Copyright © NetPing east Co., Ltd / E-mail:
below safe range
in safe range
above safe range
Normal
Alarm!
off
failed
Log.0
Log.1
off
on
reset
suspense
restore
activation
SMS not a command
SMS from unknown numbers
". There must be a space between the closing square bracket and the message text. For example,
SMS
" page of the device's web interface and marked with a "
webhook.netping.ru
–HTTP(URL) -->
Subj
" entry field (substitutions are possible) and the text of the email message
The name of the variable value
from NetPing MIB
support@netpingdevice.com www.netpingdevice.com
/
Temperature of a humidity sensor has dropped below safe range
Temperature of a humidity sensor has returned to safe range
Temperature of a humidity sensor has risen above safe range
Readings are normal
The sensor detected the smoke
The sensor (current in the loop) is switched off
The sensor failure
Logic line level switched to 0
Logical line level switched to 1
The relay is off
The relay is on
 The "
Watchdog
" module carried out the reset of the relay
The operation of the module is suspensed
The operaion of the module is restored
The signal has been activated by logic. So, the rule of logic worked,
the output of it is the "Signal 1..4". More details about the rules of
logic and, in particular, the signal can be found in the
10.2. [DKSF 48.5 IU] How Can I Use the "LOGIC" Module?
 Incoming SMS is not a command
An incoming SMS from an unknown number (subject to the setting of
white lists of numbers). Read more about setting up white lists in the
section: [ENG] 12.2. [DKSF 48.5 IU] I Need to Configure the Number
to Send SMS Notifications SMS-уведомлений. How Can I Do This?