Outside Finish Installation (Non Cool Wall) - Clearances - Regency Fireplace Products Grandview G800EH Owners & Installation Manual

Medium dv gas fireplace
Table of Contents

Advertisement

installation

Outside Finish Installation (Non Cool Wall) - Clearances

The clearances listed below are minimum distances unless otherwise stated:
A major cause of chimney related fires is failure to maintain required clearances (air space) to combustible materials. It is of the greatest
importance that this fireplace and vent system be installed only in accordance with these instructions.
Caution Requirements
The top, back and sides of the fireplace are defined by
standoffs. The metal ends of the standoff may NOT be
recessed into combustible construction.
G800EH Outside Finish Clearance Requirements
Clearance:
A: Mantel Height (min.)
B: Sidewall
C: Ceiling
D: Mantel Depth (max.)
E: Alcove Width
F: Alcove Depth
Notes:
See mantle chart on next page.
C
D
E
F
Alcove
38
| Grandview
G800EH Gas Fireplace
®
Dimension
20" (508mm)
25" (635mm) one side only
36-1/2" (927mm)
12" (305mm)
84" (2134mm)
36" (914mm)
0"
if these clearances (air space) to combustible materials are
not adhered to. It is of greatest importance that this fireplace
and vent system be installed only in accordance with these
Measured From:
Top of Fireplace Opening
Side of Fireplace Opening
Top of Fireplace Opening
Top of Fireplace Opening
Wall to Wall (Minimum)
Front to Back Wall (Maximum)
No Hearth Required
Minimum Vent Clearances
to Combustibles
Horizontal Top
Horizontal Side
Horizontal Bottom
Vertical Vent
WARNING
Fire hazard is an extreme risk
instructions.
2" (51mm)
1-1/2 " (38mm)
1-1/2" (38mm)
1-1/2" (38mm)