Chase Enclosure (Cool Wall)

When choosing to install the ventilation openings from the front, the top of the ventilation opening must be flush with the top of the chase enclosure for all
installations.
Minimum height of enclosure from base of appliance is 82" (2083mm).
A minimum 107in
opening in the enclosure is required to maintain safe operating temperatures. This can be achieved in a number of ways including the
2
examples shown in this manual.
IMPORTANT:
Exterior wall/Alcove enclosure: When installing into an exterior cavity or alcove enclosure (ceiling, back and sides), regardless of where appliance is
placed within the home, requires the use of either drywall or other means such as plywood, wood studs, etc. to prevent heat from escaping anywhere above
/through the enclosure other than the required grill / ventilation opening.
Internal chase: When installing as an internal chase framing installation ,regardless of where appliance is placed within the home, requires the use of either
drywall or other means such as plywood, on the rear wall of the chase to eliminate heat escaping into the rear wall cavity. If the chase is extended to the
ceiling ,the ceiling will also need to be finished in a manner to prevent heat escaping into floor joist/attic space.
One of the following methods must be used to prevent the heat from escaping.
a. If choosing drywall, ensure that the drywall is butt up tight with no gaps.
b. Plywood, wood studs, etc. installed tightly with no gaps.
As this appliance has been designed with all hot air escaping through the chase enclosure ventilation/grill openings only, if hot air is trapped as a result of
the hot air escaping through joints, crevasses, open studs, or other openings within the enclosure above, this will change the clearances within the enclosure
causing the enclosure to overheat. It is vital that all the hot air from within the enclosure exits through the ventilation openings only.
Ensure that the ventilation openings are made as such to prevent debris, objects from falling into the enclosure.
Warning: DO NOT cover or place objects in front of the ventilation opening air outlet(s).
Example 1: Ventilation opening in chase wall, lower than room ceiling
Room ceiling
Enclosure ceiling must be ush
with ventilation opening
Stud
Enclosure ceiling
Minimum 107sq. inch opening
Example: 3 1/4" x 33"
Fireplace Chase
Enclosure
Example 2: Ventilation opening reveal at room ceiling
Room ceiling
Minimum 107sq. inch opening
installation
Fireplace Chase
Enclosure
Grandview
G800EH Gas Fireplace |
®