Clean Front Installation (Non Cool Wall) - Clearances

The clearances listed below are minimum distances unless otherwise stated:
A major cause of chimney related fires is failure to maintain required clearances (air space) to combustible materials. It is of the greatest
importance that this fireplace and vent system be installed only in accordance with these instructions.
Caution Requirements
The top, back and sides of the fireplace are defined by
standoffs. The metal ends of the standoff may NOT be
recessed into combustible construction.
G800EH Clearance Requirements
Clearance:
A : M a n t e l H e i g h t
(min.)
B: Sidewall
C: Ceiling
D : M a n t e l D e p t h
(max.)
E: Alcove Width
F: Alcove Depth
Notes:
See mantle chart on next page.
C
D
E
F
Alcove
Dimension
Measured From:
20" (508mm)
Top of Fireplace Opening
25" (635mm)
Side of Fireplace Opening
36-1/2" (927mm)
Top of Fireplace Opening
12" (305mm)
Front of Fireplace Opening
84" (2134mm)
Wall to Wall (Minimum)
36" (914mm)
Front to Back Wall (Maximum)
0"
No Hearth Required
WARNING
Fire hazard is an extreme risk
if these clearances (air space) to combustible materials are
not adhered to. It is of greatest importance that this fireplace
and vent system be installed only in accordance with these
instructions.
The HeatWave Duct Kit has different
clearance and framing requirements, check
the HeatWave manual for details.
Minimum Vent Clearances
to Combustibles
Horizontal Top
2" (51mm)
Horizontal Side
1-1/2 " (38mm)
Horizontal Bottom
1-1/2" (38mm)
Vertical Vent
1-1/2" (38mm)
Grandview
installation
G800EH Gas Fireplace |