Clean Front Installation (Non Cool Wall)—Clearances
The clearances listed below are minimum distances unless otherwise stated:
A major cause of chimney related fires is failure to maintain required clearances (air space) to combustible materials. It is of the greatest importance
that this fireplace and vent system be installed only in accordance with these instructions.
Caution Requirements
The top, back and sides of the fireplace are defined by
standoffs. The metal ends of the standoff may NOT be
recessed into combustible construction.
G600EC Clearance Requirements
Clearance:
A: Mantel Height (min.)
B: Sidewall
C: Ceiling
D: Mantel Depth (max.)
E: Alcove Width
F: Alcove Depth
Notes:
C
D
E
F
Alcove
Dimension
Measured From:
14" (356 mm)
Top of Fireplace Opening
25" (635 mm)
Side of Fireplace Opening
36" (914 mm)
Top of Fireplace Opening
17" (432 mm)
Front of Fireplace Opening
84" (2134 mm)
Wall to Wall (Minimum)
36" (914 mm)
Front to Back Wall (Maximum)
0"
No Hearth Required
WARNING
Fire hazard is an extreme risk
if these clearances (air space) to combustible materials are not
adhered to. It is of greatest importance that this fireplace and vent
system be installed only in accordance with these instructions.
Minimum Vent Clearances
to Combustibles
Horizontal Top
Horizontal Side
Horizontal Bottom
Vertical Vent
Grandview® G600EC Gas Fireplace
installation
The HeatWave Duct Kit
has different clearance
and framing require-
ments, check the Heat-
Wave manual for details.
2" (51mm)
1-1/2 " (38mm)
1-1/2" (38mm)
1-1/2" (38mm)
|
31