Errors Related To Message Communications; Fins Message Errors (Cs/Cj-Series) - Omron CompoNet MX2 Series User Manual

Inverter, communications unit
Hide thumbs Also See for CompoNet MX2 Series:
Table of Contents

Advertisement

6 Troubleshooting
6-4
Errors Related to Message Communi-
cations
To send a CompoNet Explicit Message from a CS/CJ-series unit, use a FINS message.
If any Explicit Message/FINS message is not completed normally, check the contents of the FINS mes-
sage response.
6-4-1

FINS Message Errors (CS/CJ-series)

The table below shows the assumed cause and corrective action for each FINS response.
FINS
Description
Response
0000
Normal comple-
tion
0101
Local node not in
network
0201
Destination node
not in network
0204
Destination node
is busy.
0205
Response timeout
1001
Command too
long
1002
Command too
short
1004
Command
format error
1005
Header error
110B
Response too
long
2609
Necessary items
not set
Additional Information
For details about FINS commands not described above, refer to CS/CJ-series Communica-
tions Commands Reference Manual (Cat. No. W342).
6 - 10
Assumed Cause
Local node is not in network.
Destination node is not in net-
work.
(MS and NS LED indicators not
indicating normal state)
Destination node receives too
much data.
Response monitor time is too
short.
Message frame was destroyed
by noise.
Command is too long.
Command is too short.
Incorrect format is used.
Destination address setting
(routing table) is incorrect.
Response is longer than maxi-
mum frame length.
Required elements are not set in
command data.
CompoNet Communications Unit User's Manual (I582-E1)
Corrective Action
Check Master Unit settings and network
configuration.
Add destination node correctly to the net-
work.
Increase number of resends or review sys-
tem so that the destination node does not
receive so many messages.
Increase length of response monitor time.
Check noise conditions and take corrective
action.
Increase number of resends.
Check command format and correct com-
mand data.
Check command format and correct com-
mand data.
Check command format and correct com-
mand data.
Check FINS command (2802) in CMND
instruction.
Set routing table correctly.
Check command format and set correct
number of elements.
Check command format and set required
elements in command data.