3 Network Startup
Reset Mode Setting
For the MX2/RX-series, by default, the Reset mode is set to Always enabled. This means that resetting
the inverter also resets the CompoNet Communications Unit, which in turn causes the communication
connection to be reset.
To prevent the communication connection from being reset when the inverter is reset, OMRON recom-
mends the following setting.
For details about this parameter, refer to the MX2 User's Manual (Cat. No. I570) or RX User's Manual
(Cat. No. I578).
Parameter
C102
Detailed CompoNet Communications Unit Settings
The CompoNet Communications Unit can be configured in more detail using inverter parameters P044,
P045, P048, and P049.
Set these parameters according to the following explanation.
 Detailed CompoNet Communications Unit Settings
Parameter
P044
P045
P048
P049
3 - 10
Description
Reset Selection
Description
Communications Error Detec-
tion Timer Setting
Operation Selection at Host
Communications Error
Operation at Idle Mode Detec-
tion Setting
Number of Poles for Rotation
Speed Setting
(For conversion to the rpm
unit used in CompoNet com-
munications)
Setting
03: Trip reset only (recommended setting)
Setting
Monitors data exchange between the inverter and the Com-
poNet Communications Unit.
Normally, this parameter is not required.
0 to 9999 in units of 0.01 s. (Default: 1.00)
0: Disabled
Sets the inverter operation if an error such as a network error
occurs.
00: Trip (Default)
01: Trip after deceleration stop
02: Ignore
03: Free-run stop
04: Deceleration stop
Sets the inverter operation in Network Idle mode. OMRON's
CompoNet Master Units do not support transition to the Net-
work Idle mode and therefore this parameter is not required.
00: Trip (Default)
01: Trip after deceleration stop
02: Ignore
03: Free-run stop
04: Deceleration stop
For other types of Remote I/O that use CompoNet communi-
cations, the number of poles on the motor is set for the Rota-
tion Rotation Speed Reference.
However, this setting is disabled for Remote I/O types that uti-
lizes Modbus communication.
This parameter is fixed to the frequency value (0.01 Hz)
regardless of the value you set.
CompoNet Communications Unit User's Manual (I582-E1)