Example Of Debugging Network Communications; Outline Of Debugging Network Communications Instructions - Omron CS Series Operator's Manual

Cx-simulator
Hide thumbs Also See for CS Series:
Table of Contents

Advertisement

Example of Debugging Network Communications

6-4 Example of Debugging Network Communications

6-4-1 Outline of Debugging Network Communications Instructions

AUDIN - 8, avenue de la malle - 51370 Saint Brice Courcelles - Tel : 03.26.04.20.21 - Fax : 03.26.04.28.20 - Web : http: www.audin.fr - Email : info@audin.fr
1. Set the Communications settings as "-" to debug a part unrelated to the
1,2,3...
network.
Select [System status] | [Settings] | [Network Communications Set-
·
tings] to display the [Network Communications Settings] window.
Set the Communications settings as "-" for all communications units.
·
2. Set the Communications settings as "Messages" for displaying the FINS
commands to check the contents of the messages.
Select [System status] | [Settings] | [Network Communications Set-
·
tings] to display the [Network Communications Settings] window.
Set the Communications settings as "Messages" for the communica-
·
tions unit to be debugged.
3. Set the Communications settings as "Local" followed by issuing
SEND/RECV instructions to the CPU Unit of FinsGateway to check the
FINS communications (only for DM and CIO).
Select [System status] | [Settings] | [Network Communications Set-
·
tings] to display the [Network Communications Settings] window.
Set the Communications settings as "Local" for the communications
·
unit to be debugged.
Change the FINS address for the control data of SEND/RECV in-
·
struction to the one for the CPU Unit of FinsGateway.
Note Confirm that the target area is not used by other application programs when
using a SEND instruction to the CPU Unit of FinsGateway.
Section 6-4
139

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents