Step Run and Break

4-3 Step Run and Break

4-3-1 Operations for Step Run

Peripheral Servicing
Online Editing
Cycle Time during Step Run

4-3-2 Break Setting

The Number of settings
For applications program
area (UM1)
For debugging program
area (UM2)
Action
When online
when a
editing
program
changed
When down-
loading
Operation after execution
AUDIN - 8, avenue de la malle - 51370 Saint Brice Courcelles - Tel : 03.26.04.20.21 - Fax : 03.26.04.28.20 - Web : http: www.audin.fr - Email : info@audin.fr
The Step Run allows to debug by step, which was impossible in debugging
using an actual CS/CJ PLC.
In addition, combining execution with a break/start point specified, and break
with I/O memory conditions (I/O break conditions) specified will allow closer
debugging.
The Step Run is available only for a program on the program area for appli-
cations (UM1), not for debugging (UM2).
The Ladder Engine accepts and process FINS commands even during a cy-
cle execution as long as it is during pausing (e.g. Step Run).
This enables monitoring the values during a cycle execution, which is usually
impossible.
When performing Online Editing to the Ladder Engine during Step Run or
pausing during a cycle, the program execution returns to the status just prior
to the cycle start and pauses (when set as Online Editing enabled for Scan
Rerun/Step Run).
The cycle time during Step Run (including pausing), for both virtual cycle time
and computer cycle time, does not include the time of pausing. Similarly, the
Timer, Clock Pulses, etc. do not operate during pausing. However, only the
time clocks the actual time if set as "computer cycle time." If set as " virtual
cycle time", the time stays unchanged during pausing because the time ac-
cumulates the virtual cycle time.
Start point
One point
Clear
Clear
Clear setting after execu-
tion
Break point
32 points max
Usable
Unusable
Clear only the break
points in the changed
task.
All clear
No change (Continuous
setting)
Section 4-3
I/O Break Condition
One condition
No change
No change
After the break condition
is met, the values of I/O
memory area within the
conditions are reevaluated
only when they have
changed.
103