I/O Memory Allocation
Address
Words
Bits
A402
A40207
A40208
A40209
A40210
A40212
216
AUDIN - 8, avenue de la malle - 51370 Saint Brice Courcelles - Tel : 03.26.04.20.21 - Fax : 03.26.04.28.20 - Web : http: www.audin.fr - Email : info@audin.fr
Name
CS/CJ-
ON when an error occurs in a
series CPU
data exchange between the CPU
Bus Unit
Unit and a CS/CJ-series CPU
Error Flag
Bus Unit (including an error in the
(Non-fatal
CS/CJ-series CPU Bus Unit it-
error)
self).
The CPU Unit will continue oper-
ating and the ERR/ALM indicator
on the front of the CPU Unit will
flash. The CS/CJ-series CPU
Bus Unit where the error oc-
curred will stop operating and the
unit number of the Unit where the
data exchange error occurred is
indicated in A417.
(This flag will be turned OFF
when the error is cleared.)
Inner Board
ON when an error occurs in a
Error Flag
data exchange between the CPU
(Non-fatal
Unit and the Inner Board (includ-
error)
ing an error in the Inner Board
itself).
The CPU Unit will continue oper-
ating and the ERR/ALM indicator
on the front of the CPU Unit will
flash. The Inner Board will stop
operating and details on the error
will be written to A424.
(This flag will be turned OFF
when the error is cleared.)
I/O Verifi-
ON when a Basic I/O Unit regis-
cation Error
tered in the I/O Table does not
Flag
match the Basic I/O Unit actually
(Non-fatal
installed in the PLC because a
error)
Unit was added or removed.
PLC Setup
ON when there is a setting error
Error Flag
in the PLC Setup. The CPU Unit
(Non-fatal
will continue operating and the
error)P
ERR/ALM indicator on the front
of the CPU Unit will flash.
The location of the error will be
written to A406.
(This flag will be turned OFF
when the error is cleared.)
Basic I/O
ON when an error has occurred
Unit Error
in a Basic I/O Unit (including
Flag
C200H Group-2 High-density I/O
(Non-fatal
Units and C200H Interrupt Input
error)
Units).
CS/CJ-series PLC
Function
1: Error in
one or
more Units
0: No error
in any Unit
1: Error
0: No error
1: Mis-
match
0: No mis-
match
1: Error
0: No error
1: Error
0: No error
Section 9-3
CX-Simulator
Settings
Function
Not used.
Not used.
Not used.
Same as
CS/CJ-series
PLC.
Not used.
Settings