I/O Memory Allocation

9-3 I/O Memory Allocation

9-3-1 PLC Setup Settings

Item
Basic I/O Unit Input
Response Time
Rack 0 to 7, Slot 0 to 9
IOM Hold Bit Status at
Startup
Forced Status Hold Bit
at Startup
Startup Mode
Detect Low Battery
196
AUDIN - 8, avenue de la malle - 51370 Saint Brice Courcelles - Tel : 03.26.04.20.21 - Fax : 03.26.04.28.20 - Web : http: www.audin.fr - Email : info@audin.fr
CS/CJ-series PLC
Settings
00: 8 ms
Sets the input response time (ON
10: 0 ms
response time = OFF response
11: 0.5 ms
time) for CS/CJ-series Basic I/O
12: 1 ms
Units. The default Setting is 8 ms
13: 2 ms
and the setting range is 0 ms to
14: 4 ms
15: 8 ms
32 ms.
16: 16 ms
17: 32 ms
Default: 00 (8
ms)
0: Cleared
This setting determines whether
1: Retained
or not the status of the IOM Hold
Bit (A50012) is retained at
Default: 0
startup.
When you want all of the data in
I/O Memory to be retained when
the power is turned on, turn ON
the IOM Hold Bit and set this
setting to 1 (ON).
0: Cleared
This setting determines whether
1: Retained
or not the status of the Forced
Status Hold Bit (A50013) is re-
Default: 0
tained at startup.
When you want all of the bits that
have been force-set or force-
reset to retain their forced status
when the power is turned on, turn
ON the Forced Status Hold Bit
and set this setting to 1 (ON).
PRCN:
This setting determines whether
Programming
the startup mode will be the
Console's mode
mode set on the Programming
switch
Console's mode switch or the
mode set here in the PLC Setup.
PRG:
(If this setting is PRCN and a
PROGRAM
Programming Console isn't con-
mode
nected, the CPU Unit will auto-
matically enter PROGRAM mode
MON: MONITOR
at startup.)
mode
RUN: RUN mode
Default: RPCN
0: Detect
This setting determines whether
1: Do not detect
CPU Unit battery errors are de-
tected. If this setting is set to 0
Default: 0
and a battery error is detected,
the Battery Error Flag (A40204)
will be turned ON.
Function
Not used.
Same as
CS/CJ-
series PLC.
Same as
CS/CJ-
series PLC.
PRCN
(fixed)
Not used.
Section 9-3
CX-Simulator
Settings
Function
As this setting is
fixed to PRCN,
the CPU Unit
will automati-
cally enter
PROGRAM
mode.