Probe Configuration Parameters - Prb - Emerson Dixell Full Touch XR20T Installing And Operating Instructions

Hide thumbs Also See for Dixell Full Touch XR20T:
Table of Contents

Advertisement

odS
Output activation delay at start-up
AC
Anti-short cycle delay
Anti-short cycle delay (2nd
AC1
compressor)
Activation mode for 2nd
2CC
compressor
rCC
Enable compressor rotation
Maximum time with compressor on
MCo
(0=disabled)
Compressor selection with hot gas
Cdd
defrost
Regulation percentage=F(P1; P2)
rtr
(100=P1; 0=P2)
CCt
Maximum duration for Pull Down
Pull Down phase differential
CCS
(SET+CCS or SET+HES+CCS)
Threshold for automatic activation
oHt
of Pull Down in normal mode
(SET+HY+oHt)
Threshold for automatic activation
oHE
of Pull Down in energy saving
mode (SET+HES+HYE+oHE)
Compressor ON time with faulty
Con
probe
Compressor OFF time with faulty
CoF
probe
5.1.2 Probe configuration parameters – Prb
LABEL
DESCRIPTION
P1C
Probe P1 selection
P2C
Probe P2 selection
P3C
Probe P3 selection
P4C
Probe P4 selection
ot
Probe P1 calibration
P2P
Probe P2 presence
oE
Probe P2 calibration
1592040000 XR20-30-60-70T EN v1.5 2023.10.12.docx
This function is enabled after the
0 to 255 min
instrument power-on and delays the
activation of the outputs.
Delay between first compressor (CP1)
0 to 50 min
stop and the next restart.
Delay between second compressor
0 to 255 min
(CP2) stop and the next restart.
FUL=delayed respect to main onoff
FUL(0); HAF(1)
compressor; HAF=step activation logic,
par. HY1 is used.
n=compressor 1 is activated always as
n(0); Y(1)
first; Y= toggle compressor 1 and
compressor 2 activation.
Define the maximum running time for
0 to 255 min
onoff compressors.
CP1=only compressor CP1 is activated
during any defrost; CP2=only
CP1; CP2; 2CC
compressor CP1 is activated during any
defrost; 2CC=both compressors CP1 and
CP2 are activated during any defrost
Weighted coefficient for double probe
(P1 and P2) regulation
0 to 100
R=P1*(rtr/100)+P2*(1-rtr/100). If rtr=100:
only P1 value is used. If rtr=0: only P2
value is used.
When this interval ends, the Pull Down
0.0 to 23h50min
function is immediately stopped
During any Pull Down, the regulation
[-12.0°C to 12.0°C]
SETPOINT is moved to SET+CCS (in
[-21.6°F to 21.6°F]
normal mode) or to SET+HES+CCS (in
energy saving mode)
This is the upper limit used to
[0.0°C to 25.0°C]
automatically activate the Pull Down
[0.0°F to 45.0°F]
function
This is the upper limit used to
[0.0°C to 25.0°C]
automatically activate the Pull Down
[0.0°F to 45.0°F]
function in energy saving mode.
Interval with compressor output ON in
0 to 255 min
case of faulty regulation probe. With
Con=0 compressor output is always OFF
Interval with compressor output OFF in
0 to 255 min
case of faulty regulation probe. With
CoF=0 compressor output is always ON
RANGE
ntC(0); Pt1(1);
ntC= NTC probe; Pt1= PT1000 probe
PtC(2)
ntC(0); Pt1(1);
ntC= NTC probe; Pt1= PT1000 probe
PtC(2)
ntC(0); Pt1(1);
ntC= NTC probe; Pt1= PT1000 probe
PtC(2)
ntC(0); Pt1(1);
ntC= NTC probe; Pt1= PT1000 probe
PtC(2); Cur(3)
[-12.0°C to 12.0°C]
Allows to adjust any possible offset of the
[-21.6°F to 21.6°F]
probe P1.
n(0); Y(1)
n = not present; Y = present
[-12.0°C to 12.0°C]
Allows to adjust any possible offset of the
[-21.6°F to 21.6°F]
probe P2.
XR20-30-60-70T
MEANING
0
0
0
FUL
no
0
2C
100
00:00
0.0
10.0
10.0
10
15
VALUE
ntC
ntC
ntC
ntC
0.0
yes
0.0
16/38