Section 4
The new correction value will appear next to the [HF] menu cell as shown below.
z

"Automatic" Adjustment

In the [Site Setup Data] Menu, press the <Down Arrow> and scroll to the [HF] menu cell. Press
z
the <Right Arrow> and a pop-up [Manual] prompt will appear.
Press the <Up or Down Arrow> to select [Automatic] then press <ENT>.
z
The current measured correction value is displayed (see below).
z
Press <ENT> again to install this correction value which will now appear next to the [HF] menu
z
cell.
NOTE: The value shown in the [Automatic] pop-up prompt can not be changed and is for user
information only.
Siemens
Dual Path
fx (drive)
N (burst length)
Ltn in
Vf max CU
Vs max m/s
Vs min m/s
Samples/Cycle
Max damping
Min Damping
HF
Site Setup Data
If you decide not to use the [Automatic] selection, press any key other than <ENT> to abort the
z
operation.
Siemens
fx (drive)
N (burst length)
Ltn in
Vf max CU
Vs max m/s
Vs min m/s
Samples/Cycle
Max Damping
Min Damping
HF
Site Setup Data
4SS10G
29
5
5.316
Adjustment
>Automatic
1355.00
29
>-0.000
Dual Path
4SS10G
29
5
5.316
1355.00
29
>-0.120
Siemens
fx (drive)
N (burst length)
Ltn in
Vf max CU
Vs max m/s
Vs min m/s
Samples/Cycle
Max Damping
Min damping
HF
Site Setup Data
4-68
1010GCNFM-3C
Dual Path
4SS10G
29
5
5.316
>Automatic
= 0.026
1355.00
29
>-0.026

Advertisement

Table of Contents
loading

Table of Contents