Pgen; Max Flow - Siemens SITRANS FUG1010 IP65 NEMA 4X Instruction Manual

Ultrasonic flowmeters
Hide thumbs Also See for SITRANS FUG1010 IP65 NEMA 4X:
Table of Contents

Advertisement

Section 4
(continued)
Vs
Spanned gas
sonic velocity:
Vsg
spanned gas
specific gravity:
Maximum span values represent: Minimum span values represent:
100% of span
Current output of 20 mA
Voltage output of 10 Vdc

PGEN

The [PGEN P/Unit Volume] menu cell entry controls a digital output pulse function and is available in
Custody Transfer units only (designated by a "C" in their part number). It allows the assigning of PGEN
digital signal pulses per unit of volume. For example, 1000 output pulses per cubic foot of gas.
NOTE: The unit of volume is determined by the Volume Units initially selected from the [Total
Volume Units] menu cell option list (refer to paragraph 4.6.6).
To assign PGEN output pulses:
From the [Span Data] menu press
From the [PGEN P/Unit Volume] menu cell, press
Use the numeric keys to enter the desired number of PGEN pulses per unit volume.
To store the data press
FUG1010GCCDN (Expanded 1010N-7 I/O Module)
TB2
PIN#
SIGNAL
9
PG1
10
PG2
11
PG3
12
PG4

Max Flow

The [Max Flow] menu cell stores the maximum range for the flow rate output (Vfo). It can be a positive
or negative value. Enter the data using the flow rate units you selected. This entry also spans the un-
signed flow variable (Vfab) as noted above.
Vs is the sonic velocity in meters-per-second (m/s) of the flowing gas.
The min. and max. Vs entries establish the Vs span. Max Vs (m/s) defines
100% of span. The Min Vs (m/s) defines 0% of span.
Vsg is the inferred operating specific gravity of the gas. The min. and
max. Vsg entries establish the Vsg span. Max Vsg defines 100% of span
and Min Vsg defines 0% span.
ENT
Installation Drawing 1010N-7-7 (Sheet 3 of 3)
(Ultra Performance Flowmeters)
FUNCTION
PRIMARY FREQUENCY OUTPUT / OPEN COLLECTOR
PRIMARY FREQUENCY OUTPUT / TTL
QUADRATURE FREQUENCY OUTPUT / OPEN COLLECTOR
QUADRATURE FREQUENCY OUTPUT / TTL
0% of span
Current output of 4 mA
Voltage output of 0 Vdc
to activate the numeric entry.
4-42
1010GCNFM-3C
NOTES
Digitally Synthesized
Pulse Waveform

Advertisement

Table of Contents
loading

Table of Contents