Smartgen HGM1790N User Manual page 18

Hide thumbs Also See for HGM1790N:
Table of Contents

Advertisement

No.
Parameter
Digital
Input
P34
Delay
P35
Power On Mode
P36
Password Set
Crank
P37
Disconnect
Condition
Disconnect
P38
Engine Speed
Disconnect
P39
Generator Freq
Disconnect
Oil
P40
Pressure
P41
AC System
Temperature
P42
Sensor
Oil
Pressure
P43
Sensor
Fuel
Level
P44
Sensor
Disconnect
Oil
P45
Pressure Delay
P46
Aux. Output 1
P47
Aux. Output 2
HGM1790N Genset Controller
HGM1790N GENSET CONTROLLER USER MANUAL
Default
Range
Value
(0-20.0)s
2.0
(0-2)
(0-9999)
0318
(0-6)
See table 5.
(0-3000) RPM
360
(10.0-30.0) Hz
14.0
(0-400) kPa
200
(0-3)
(0-10)
06
(0-10)
06
(0-7)
(0-20.0)s
0.0s
(0-9)
(0-9)
2017-10-09
value is 8, fuel level sensor type can be
selected.
Active delay time for digital input ports
0
0: Shutdown 1: Auto 2:Manual
Starter motor disconnection condition.
There are 3 conditions of disconnecting
starter with engine (magnetic pickup,
1
generator frequency and oil pressure).
Aiming at to separate the start motor and
genset as soon as possible.
When generator speed is higher than the
set value, starter will be disconnected.
When generator frequency higher than
the
set
value,
disconnected.
When generator oil pressure higher than
the set value, starter will be disconnected
and oil engine crank successfully.
0:3P4W
2:1P2W
2
It is used for calculating generator
voltage and active power.
SGD (120ºC resistor type)
SGD (10Bar resistor type)
Not used. (If fuel level sensor is used,
0
then the digital input port must be set as
„not used‟.
When
crank
including oil pressure, and engine oil
pressure and delay value are higher than
set values, starter will be disconnected
and oil engine crank successfully.
3
Default: Idle Speed Output
2
Default: ETS Output
Version1.1
Description
starter
will
1:2P3W
3:3P3W
disconnect
condition
Page 18 of 27