Icons
Alarms
Gen Over Current Warn Warn Alarm
Gen Over Current Shut Shut Alarm
Gen
Over
Cooling Shut
Gen Over Volt Shut
Gen Low Volt Shut
Fail to Start
Auxiliary
Shut
Input
Low Fuel Level Warn
Low Fuel Level Input
Warn
Fuel
Level
Open/Short Circuit Shut
Fail to Stop
Low Battery Volt Warn
High Battery Volt Warn
HGM1790N Genset Controller
HGM1790N GENSET CONTROLLER USER MANUAL
Type
Controller sent alarms when generator current is
higher than the preset value and over current action
is selected as "Warn".
Controller sent alarms when generator current is
higher than the preset value and last for over than
the delay value (over current action is selected as
"Shutdown").
Controller sent alarms when generator current is
Current
higher than the preset value and last for over than
Shut Alarm
the delay value (over current action is selected as
"Cooling Shutdown").
Detection after safe running delay, controller sent
alarms when generator voltage is higher than over
Shut Alarm
voltage threshold and last for over than voltage
abnormal delay value.
Detection after safe running delay, controller sent
alarms when generator voltage is lower than under
Shut Alarm
voltage threshold and last for over than voltage
abnormal delay value.
Controller Sent alarms when genset fail to start in
Shut Alarm
Controller sent alarms when auxiliary input port,
Warn
which is configured as "auxiliary shutdown alarm
Shut Alarm
input", is active.
Controller sent alarms when fuel level is lower than
Warn Alarm
low fuel level threshold and last for over 10s.
Controller sent alarms when low fuel level input is
Warn Alarm
Controller sent alarms when Fuel level sensor
Sensor
Warn Alarm
resistance value is above 6000ohm or under 5
ohm.
Controller sent alarms when genset fail to stop in
Warn Alarm
stop duration.
Controller sent alarms when battery voltage is
Warn Alarm
lower than under voltage threshold and last for over
20s.
Controller sent alarms when battery voltage is
Warn Alarm
higher than over voltage threshold and last for over
20s.
2017-10-09
Triggering Condition
preset attempts.
active.
Version1.1
Page 12 of 27