Table 10. External Regeneration Resistor Setting - Parker P Series User Manual

Ethercat drive
Hide thumbs Also See for P Series:
Table of Contents

Advertisement

D. Regeneration brake power setting (0x200C)
-
Set the power of the external regeneration brake to [W]Unit.
-
The value should be set if the regeneration brake setting (0x2009) is 1.
-
Default value: 0
E. Regeneration brake peak power and duration setting (0x200D, 0x200E)
-
Set the power and time to the peak power and the duration time provided
by the data sheet of the external regeneration brake
-
When there is no separately provided values, set the peak power to 5
times the regeneration brake power setting(0x200C), and set the duration
time to 5000[ms] (the exact values may vary depending on the
regeneration brake specifications and brakes)
-
The value should be set if the regeneration brake setting (0x2009) is 1.
The specifications of the optional regeneration brake provided by us for use of
external regeneration brake are as follows
Drive Power
100W
200W
400W
1KW
3.5KW

Table 10. External Regeneration Resistor Setting

3.6.3
You can set the regeneration brake derating factor(0x200A) based on consideration of
the installation environment and heat protection condition. If the heat protection
condition is poor, use the brake after derating (below the power).
When derating (set the vale to 100 or below), the regeneration overload alarm (AL-23)
sets off faster if the set value is smaller.
If you want to set the derating factor to 100% or above, you should fully consider the
heat protection condition of the installed drive.
Parker Hannifin
Resistance
Brake Power
50Ω
30Ω
30Ω
Other Consideration
P series EtherCAT Drive User Guide
140W
APCS-140R50
300W
APCS-300R30
600W
APC-600R30
Model
35