Modifying Occupancy Sensor Response

The WaveLinx Mobile Application allows modification of some occupancy sensor functions at the individual sensor level and other functions
at a grouped level called an occupancy set. An occupancy set is a group of occupancy sensors that operate together to control the space.
When an area is created, any occupancy sensor assigned to the area is automatically grouped into a default occupancy set to control the
loads in the area. This includes fixture integrated sensors and battery powered ceiling sensors.
In some applications, modification of default occupancy sensor settings may be necessary to meet the desired response. This section
discusses changes that can be made, including:

Adjusting occupancy set response and controlled zones

Adjusting individual occupancy sensor settings
Defining additional occupancy sets
Associating occupancy sets for overlapping or cascading control
Deleting occupancy sets
Adjusting Occupancy Set Response and Controlled Zones
The occupancy set programming defines the response for all sensors within that set for the controlled zones. Remember that when an
area is created, fixture integrated sensors and battery powered ceiling sensors that are assigned to an area are automatically grouped into a
default occupancy set. The occupancy set automatically controls the default zones for the area. If zones have been manually added, it may be
necessary to manually assign them to the occupancy set control group.
The automatic code commissioning programming defaults for all occupancy sets are:
Mode: Occupancy
Hold Time: 20 minutes
Occupied: Select Scene 3 (default 50% level)
Unoccupied: Select Scene 0 (default 0% or OFF level)
Controls default zones for the area (zones 1, 2 and 3)
Any of these parameters may be modified for the occupancy set.
To modify the occupancy set response and controlled zones:
Step 1: Open the WaveLinx Mobile Application and establish a connection with the Wireless Area Controller as the administrator user.
Step 2: In the areas list, select the area that contains the desired occupancy set.