Step 5: Use the minimum level and maximum level adjustments to select the desired trim values. Touch the save button to save the change.
It is possible to assign a dimmable fixture to a non-dimmable zone to allow it to act like a switched load. In this instance, a maximum level may be set
N
ote:
to set a high end trim. The dimmable fixture will turn ON to the defined maximum level when commanded to any level of 1% or higher when left in the default
First On/Last Off operation mode.

Modifying Zone Operational Mode

It is rare to adjust the zone operation mode from the First On/Last Off behavior default. This feature might be used in locations where
dimming fixtures and non-dimming (switched) loads are in the same space and need to operate together in the same lighting zone. In this
circumstance, the operational mode setting determines how the switched and dimmed load should operate. For instance, if a dimmable
zone has a switched load assigned to it as well as dimmable loads, it may be desirable to have the switched load turn OFF when starting to
dim the dimmable loads. This prevents the switched load from continuing to be ON full bright while other loads in the zone are dimming. It
may also be desirable to have the switched load turn ON last so that dimmable loads in the zone can fade gradually to the chosen light level
before the switched loads turn ON. This type of modification is done by adjusting the default operational mode First ON/Last OFF behavior.
(Note that adjustment of the operational mode affects only the switched load assigned to the dimmable zone. The dimmable loads in the
zone will not be affected by the change in operation mode.)
To modify the default operational mode:
Before beginning, assign the switched load to the same zone as the dimmed lighting that it needs to operate with.
Step 1: Open the WaveLinx Mobile Application and establish a connection with the Wireless Area Controller as the administrator user.
Step 2: In the areas list, select the area to be modified.
Adjust the minimum and
maximum levels
Save the settings