Simulation - Emerson Rosemount 3051CF Series Reference Manual

Pressure transmitter with foundation fieldbus protocol
Hide thumbs Also See for Rosemount 3051CF Series:
Table of Contents

Advertisement

Reference Manual
00809-0100-4774
Run - Default State
Resource - Not Used
Defaults - Sets all device parameters to F
Processor - Does a software reset of the CPU
5.7

Simulation

Simulate replaces the channel value coming from the Sensor Transducer Block. For testing
purposes, you can manually drive the output of the Analog Input Block to a desired value.
There are two ways to do this.
5.7.1
Manual mode
To change only the OUT_VALUE and not the OUT_STATUS of the AI Block, place the
TARGET MODE of the block to MANUAL. Then, change the OUT_VALUE to the desired
value.
5.7.2
Simulate
Procedure
1. If the SIMULATE switch is in the OFF position, move it to the ON position.
2. To change both the OUT_VALUE and OUT_STATUS of the AI Block, set the TARGET
3. Set SIMULATE_ENABLE_DISABLE to Active.
4. Enter the desired SIMULATE_VALUE to change the OUT_VALUE and
5. Set SIMULATE_ENABLE_DISABLE to Inactive to return the AI block to normal
Reference Manual
MODE to AUTO.
SIMULATE_STATUS_QUALITY to change the OUT_STATUS.
operation.
Operation and maintenance
Fieldbus default values
OUNDATION
July 2020
101