Emerson Rosemount 3051CF Series Reference Manual page 114

Pressure transmitter with foundation fieldbus protocol
Hide thumbs Also See for Rosemount 3051CF Series:
Table of Contents

Advertisement

Troubleshooting
July 2020
6.6.7
Variation change detected
NE107 and Plantweb
The statistical process monitor has detected either a mean variation or high or low
dynamics in the process.
Recommended actions
Default configuration
Enabled
LCD display message
^^^^^SPM^ALERT
Associated status bits
0x00000008
6.6.8
Alert simulation enabled
NE107 and Plantweb
Alert simulation is enabled. The active alerts are simulated, and any real alerts are
suppressed.
Recommended action
Default configuration
Enabled
LCD display message
N/A
Associated status bits
FD_SIMULATE.ENABLE 0x02
6.6.9
Function check
NE107 alert: Function Check; Plantweb
The sensor transducer block mode is not in Auto.
Recommended actions
114
alert: Maintenance
Check the statistical process monitor status in the diagnostics transducer block.
Check for plugged impulse lines.
alert: Maintenance
To view real alerts, disable the alerts simulation.
Check if any transducer block is currently under maintenance.
alert: Advisory
Reference Manual
00809-0100-4774
Rosemount 3051