2.4

Node address

The transmitter is shipped at a temporary (248) address. This enables F
Fieldbus host systems to automatically recognize the device and move it to a permanent
address.
2.5

General block information

2.5.1
F
OUNDATION
Reference information on the process control function blocks can be found in the Function
Block
Resource block
The resource block contains diagnostic, hardware, and electronics information. There are
no linkable inputs or outputs to the resource block.
Sensor transducer block
The sensor transducer block contains sensor information including the sensor diagnostics
and the ability to trim the pressure sensor or recall factory calibration.
LCD display transducer block
The LCD display transducer block is used to configure the LCD display meter.
Statistical process monitoring (SPM) block
The SPM block is available on a new transmitter if the D01 option is ordered.
With this block, you can view, configure, and monitor the statistical process monitoring
diagnostics used for process monitoring and plugged impulse line detection.
Analog input block
The analog input (AI) function block processes the measurements from the sensor and
makes them available to other function blocks. The output value from the AI block is in
engineering units and contains a status indicating the quality of the measurement. The AI
block is widely used for scaling functionality.
22
(continued)
Fieldbus function blocks
Reference
Manual.