7.5 Cleaning a condensate trap

1.
Unscrew the union nut.
Condensate traps should be checked annually, cleaned and
refilled as necessary. Before cleaning the condensate trap,
you must turn off the power to the boiler, and allow it to cool
down.
Important: Installers or service contractors should ensure
that the end user is instructed on cleaning and refilling the
trap.
Warning
If condensate neutralization is used, check the pH
level of condensate before and after neutralization
to verify effectiveness and ensure that the
discharge has neutral pH levels. Never operate the
boiler unless the trap is filled with water. Failure to
comply will result in severe personal injury or
death.
2.
Rotate the elbow sideways, so that you
can remove the condensate trap base.
103