Maximum Ignition Trials Error - IBC Sl Series Installation & Operating Manual

Residential condensing boiler
Hide thumbs Also See for Sl Series:
Table of Contents

Advertisement

8.2.1 Maximum ignition trials error

Issue
Error – Ignition Failure
after 3 tries boiler has
failed to ignite on 3
successive attempts.
Boiler is in lockout for 1
hour, then repeats 3-try
sequence. Consult service
technician if error recurs.
Maximum Ignition Trials Error
Diagnosis
No spark when
Check that ignition lead is secure at the
igniting. Ignition
control module and at the probe.
probe/flame sensor
disconnected.
Manual gas shutoff is
Check for gas flow. Open manual gas
closed or gas line not
shutoff and reset boiler.
fully purged.
Gap between ignition
Adjust ignition probe rod gap between ⅛
probe rods is too
and 3/16th inch (3.2-4.7 mm).
large or too small.
Spark, but no ignition Check that the spark module is sending
power to the gas valve - close the gas
supply, then disconnect the (black) electric
housing from the face of the gas valve.
Gently spread the plastic tabs to open. Look
for 24 VAC voltage during an ignition cycle.
Replace the module if there is no current
detected.
Boiler ignites, but
Ensure the pressure vessel is grounded.
shuts off at the end of
Check the ignition probe/flame sensor is
the ignition trial.
electrically isolated from the vessel, and its
Improperly grounded
ceramic insulator is intact. Replace ignition
pressure
lead Replace spark module.
vessel/burner or
unserviceable
ignition lead or spark
module.
93
8.2.1 Maximum ignition trials error
Fix

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Sl 10-85 g3Sl 14-115 g3Sl 20-160 g3Sl 30-199 g3

Table of Contents